Chapter 5) 7SR23 DAD Installation Guide
©2013 Siemens Protection Devices Limited
Chapter 5 Page 9 of 24
PANEL CUT-OUT
182
201.5
9.75
FRONT VIEW
207.5
Diameter 3.6 - 4 holes (see note 1)
Case Earth connection
TOP VIEW
75mm MIN CLEARANCE BELOW EN100 MODULE
FOR ETHERNET COMMS CONNECTIONS
Optional
ethernet
comms
module
FRONT
SIDE VIEW
31
216.5
25mm MIN CLEARANCE FOR TERMINAL WIRING
70mm MIN CLEARANCE FOR F/O COMMS CABLE
11
Case Earth connection
Typical
when
fitted
Optional ethernet
comms module
254.5
See note 2
NOTES:
1) THE 3.6 HOLES ARE FOR M4 THREAD FORMING (TRILOBULAR) SCREWS. THESE ARE SUPPLIED AS STANDARD AND
ARE SUITABLE FOR USE IN FERROUS / ALUMINIUM PANELS 1.6mm THICK AND ABOVE. FOR OTHER PANELS, HOLES TO
BE M4 CLEARANCE (TYPICALLY 4.5 DIAMETER) AND RELAYS MOUNTED USING M4 MACHINE SCREWS, NUTS AND
LOCKWASHERS (SUPPLIED IN PANEL FIXING KIT).
2) ACCESS CLEARANCE REQUIRED FOR OPTIONAL ETHERNET COMMS MODULE RETAINING SCREW
Figure 3.1-2 Overall Dimensions and panel Drilling for Size E8 Epsilon case