Chapter 4) 7SR23 DAD Data Communications
©2013 Siemens Protection Devices Limited
Chapter 4 Page 10 of 54
Setting name
Range
Default
Setting
Notes
Station Address
1 – 254 for IEC60870-5-103
0 – 247 for Modbus RTU
0 – 65520 for DNP3.0
0
As Required
An address within the range of
the relevant protocol must be
given to identify the relay. Each
relay must have a unique
address.
COM3 Protocol
OFF, IEC60870-5-103,
MODBUS-RTU, DNP3.0,
IEC61850
IEC60870-5-
103
As Required
Sets the protocol used to
communicate on the connection
– Com3
COM3 Baud Rate
75 110 150 300 600 1200
2400 4800 9600 19200
38400 57600 115200
19200
As Required
The baud rate set on all of the
relays connected to the control
system must be the same as
the one set on the master
device.
COM3 Parity
NONE, ODD, EVEN
EVEN
As Required
The parity set on all of the
relays connected to the control
system must be the same and
in accordance with the master
device.
COM3 Line Idle*
LIGHT ON, LIGHT OFF
LIGHT OFF
As Required
Sets the idle state of the line in
accordance with master device
COM3 Data Echo*
ON,OFF
OFF
As Required
Set to ON when relays are
connected in a ring
configuration.
COM4 Protocol**
OFF, IEC60870-5-103,
MODBUS-RTU, DNP3.0
IEC60870-5-
103
As Required
Sets the protocol used to
communicate on the connection
– Com4.
COM4 Baud Rate**
75 110 150 300 600 1200
2400 4800 9600 19200
38400
19200
As Required
The baud rate set on all of the
relays connected to the control
system must be the same as
the one set on the master
device.
COM4 Parity**
NONE, ODD, EVEN
EVEN
As Required
The parity set on all of the
relays connected to the control
system must be the same and
in accordance with the master
device.
COM4 Line Idle**
LIGHT ON, LIGHT OFF
LIGHT OFF
As Required
Sets the idle state of the line in
accordance with master device
COM4 Data Echo**
ON,OFF
OFF
As Required
Set to ON when relays are
connected in a ring
configuration.
*Not applicable for RS 485 or RS 232 options
**COM 4 is fibre optic only