Chapter 7) 7SR23 DAD Applications Guide
©2013 Siemens Protection Devices Limited
Chapter 7 Page 33 of 42
6.2.5
3 Phase Differential Plus Earth Fault Configuration
3 Pole Diff
PROTECTED
ZONE
(Connections
Or
Busbars)
Transformer
Incomer
7SR23 DAD
I
A
I
B
I
C
I
G
87/
50-1
87/
50-2
CT50
87/
50-1
87/
50-2
CT50
87/
50-1
87/
50-2
CT50
87
REF
2
87
REF
1
50G
(x2)
SYSTEM CONFIG
> Relay Config
> 3 Pole Diff + EF
High Impedance
Components
Figure 6-4
MV Busbar Protection with EF Check
This application may be utilised in an MV distribution system, a self check system is provided using a single relay.
The relay is configured such that operation of either two phase fault differential elements or a phase fault
differ earth fault (50G) is required before an output trip command is issued.