Chapter 4) 7SR23 DAD Data Communications
©2013 Siemens Protection Devices Limited
Chapter 4 Page 5 of 54
Section 2: Physical Connection
As standard the relay provides one ‘Front’ USB communication interface (COM2) located on the fascia and one
RS485 (COM1) located on the ‘Rear’.
Optionally additional fibre optic (x2), RS232 (x1), RS485 (x1) or Ethernet comms ports can be provided on the
rear, these are designated COM3 or COM4 as detailed below.
1. COM1-RS485: this port can be used for IEC60870-5-103, MODBUS RTU or optionally DNP3
communications to a substation SCADA or integrated control system or engineer remote access.
2. COM2-USB: this port is used for IEC60870-5-103 (default setting) communication with Reydisp software.
MODBUS RTU or optional DNP3 are also available via COM2.
An ASCII protocol, the main use of which is to allow firmware to be updated from the front connection, is
also available through this port.
Access to COM2 settings is only available from the relay front fascia via the
COMMUNICATIONS MENU
3. COM3: Located on the rear of the relay this optional port can be used for IEC60870-5-103, MODBUS
RTU, DNP 3 or optional IEC61850 communications to a substation SCADA, integrated control system or
for engineer remote access.
4. COM4: Located on the rear of the relay thise optional port can be used for IEC60870-5-103, MODBUS
RTU or DNP3 communications to a substation SCADA or integrated control system or engineer remote
access.
SPDL can provide a range of interface devices, please refer to product portfolio catalogue.
Full details of the interface devices can be found by referring to the website
www.energy.siemens.com
.