Chapter 1) 7SR23 DAD Description Of Operation
©2013 Siemens Protection Devices Limited
Chapter 1 Page 22 of 36
3.4.3 ‘REF1 + REF2’ Operation
The relay is configured for ‘REF1 + REF2’ operation using the
SYSTEM CONFIG > Relay Config > REF1 +
REF2
setting.
When configured in this way the relay uses both 87REF elements. 87REF-1 earth current is measured by the
earth current input, 87REF-2 current is measured by the I
B
current input. These elements operate independently
of each other.
For detailed information on the restricted earth fault functions refer to section 3.3.
Figure 3-7
Logic Diagram: ‘REF1 + REF2’ Protection