6.6 Operating Mode
The relay has three operating modes, Local, Remote and Out of Service. The following table identifies the
functions operation in each mode.
The modes can be selected by the following methods:
SYSTEM CONFIG>
RELAY MODE
setting, a Binary Input or Command
OPERATION
REMOTE
LOCAL
OUT OF SERVICE
Control
Rear Serial Ports (when set as Remote)
Enabled
Disabled
Disabled
Rear Serial Ports (when set as Local)
Disabled
Enabled
Disabled
Fascia (Control Mode)
Disabled
Enabled
Disabled
USB
Disabled
Enabled
Disabled
Binary Inputs
Setting Option
Setting Option
Enabled
Binary Outputs
Enabled
Enabled
Disabled
Reporting
Spontaneous
IEC 103
Enabled
Enabled
Disabled
DNP3
Enabled
Enabled
Disabled
General Interrogation
IEC 103
Enabled
Enabled
Disabled
DNP3
Enabled
Enabled
Disabled
MODBUS
Enabled
Enabled
Enabled
Changing of Settings
Rear Ports (when set as Remote)
Enabled
Disabled
Enabled
Rear Ports (when set as Local)
Disabled
Enabled
Enabled
Fascia
Enabled
Enabled
Enabled
USB
Disabled
Enabled
Enabled
Historical Information
Waveform Records
Enabled
Enabled
Enabled
Event Records
Enabled
Enabled
Enabled
Fault Information
Enabled
Enabled
Enabled
Setting Information
Enabled
Enabled
Enabled
Table 6-1
Operating Mode
6.7 Control Mode
This mode provides convenient access to commonly used relay control and test functions. When any of the items
listed in the control menu are selected control is initiated by pressing the ENTER key. The user is prompted to
confirm the action, again by pressing the ENTER key, before the command is executed.
Control Mode commands are password protected using the Control Password function – see Section 6.10.