Chapter 4) 7SR23 DAD Data Communications
©2013 Siemens Protection Devices Limited
Chapter 4 Page 38 of 54
OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Number
Description
Function Codes
(dec)
Qualifier Codes
(hex)
Function Codes
(dec)
Qualifier
Codes (hex)
32
1
(default
1)
)
32-Bit Analog
Change Event
without Time
1
(read)
06(no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28
(index)
32
2
16-Bit Analog
Change Event
without Time
1
(read)
06(no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28
(index)
32
3
32-Bit Analog
Change Event with
Time
1
(read)
06(no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28
(index)
32
4
16-Bit Analog
Change Event with
Time
1
(read)
06(no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28
(index)
32
5
short floating point
Analog Change Event
without Time
1
(read)
06(no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28
(index)
32
6
long floating point
Analog Change Event
without Time
1
(read)
06(no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28
(index)
32
7
short floating point
Analog Change Event
with Time
1
(read)
06(no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28
(index)
32
8
long floating point
Analog Change Event
with Time
1
(read)
06(no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28
(index)
50
0
Time and Date
1(read)
07, (limited qty = 1)
129 (response)
07 (limited qty = 1)
50
1
(default
1)
)
Time and Date
2(write)
07 (limited qty = 1)
50
3
Time and Date Last
Recorded Time
2 (write)
07
(limited
qty)
51
1
Time and Date CTO
129 (response)
130 (unsol. resp)
07
(limited qty)
(qty = 1)
51
2
Unsynchronized Time
and Date CTO
129 (response)
130 (unsol. resp)
07
(limited qty)
(qty = 1)
52
1
Time Delay Coarse
129 (response)
07
(limited qty)
(qty = 1)
52
2
Time Delay Fine
129 (response)
07
(limited qty)
(qty = 1)
60
0
Not Defined
60
1
Class 0 Data
1
(read)
06(no range, or all)
1
(read)
06(no range, or all)
07, 08 (limited qty)
60
2
Class 1 Data
20 (enbl. unsol.)
21 (dab. unsol.)
22 (assign class)
06(no range, or all)
1
(read)
06(no range, or all)
07, 08 (limited qty)
60
3
Class 2 Data
20 (enbl. unsol.)
21 (dab. unsol.)
22 (assign class)
06(no range, or all)
1
(read)
06(no range, or all)
07, 08 (limited qty)
60
4
Class 3 Data
20 (enbl. unsol.)
21(dab. unsol.)
22 (assign class)
06(no range, or all)
1(read)
00, 01(start-stop)
129 (response)
00, 01 (start-stop)
80
1
Internal Indications
2
(write)
(see
3)
)
00
(start-stop)
index=7
No Object (function
code only)
13 (cold restart)
No Object (function
code only)
14 (warm restart)
No Object (function
code only)
23(delay meas.)
No Object (function
code only)
24
(record current time)
Summary of Contents for 7SR23 DAD
Page 1: ...Answers for energy 7SR23 DAD High Impedance Protection Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR23 DAD Contents 2013 Siemens Protection Devices Limited ...
Page 60: ...Chapter 3 7SR23 DAD Performance Specification 2013 Siemens Protection Devices Limited ...
Page 225: ......