Parameter
Min
Max
Default value
Settings > Digital Input-Output
Digital input (for each input)
Stop signal, Restart signal, Muting
group “N”, Activate dynamic
configuration, Fieldbus controlled
Not configured
Digital output (for each output)
System diagnostic signal, Muting
enable feedback signal, Fieldbus
controlled, Restart Feedback signal,
Detection signal "N"
Not configured
OSSD Pulse width
Short (300 μs), Long (2 ms)
Short (300 μs)
Settings > Muting
Group for muting (for each sensor)
None, Group 1, Group 2, both
Group 1
Pulse width (for each Input TYPE)
0 μs (= Period
and Phase shift
disabled)
200 μs
2000 μs
0 μs
Period (for each Input TYPE)
200 ms
2000 ms
200 ms
Phase shift (for each Input TYPE)
0.4 ms
1000 ms
0.4 ms
Settings > Restart parameters
Protective field 1, 2, 3, 4
Automatic, Manual, Safe manual
Automatic
Settings > Multi-control synchronization
Control channel
0
3
0
Settings > Activity History
Log verbosity level
0
5
0
Settings > Network Parameters
IP Address
-
192.168.0.20
Netmask
-
255.255.255.0
Gateway
-
192.168.0.1
TCP port for configuration
1
65534
80
Settings > Fieldbus Parameters
System configuration and status
PS2v6
1
65535
145
Sensors information PS2v6
1
65535
147
Sensor 1 detection status PS2v6
1
65535
149
Sensor 2 detection status PS2v6
1
65535
151
Sensor 3 detection status PS2v6
1
65535
153
Sensor 4 detection status PS2v6
1
65535
155
Sensor 5 detection status PS2v6
1
65535
157
Sensor 6 detection status PS2v6
1
65535
159
System configuration and status
PS2v4
1
65535
146
Sensors information PS2v4
1
65535
148
Sensor 1 detection status PS2v4
1
65535
150
Sensor 2 detection status PS2v4
1
65535
152
Sensor 3 detection status PS2v4
1
65535
154
Sensor 4 detection status PS2v4
1
65535
156
9 TECHNICAL REFERENCES
8027489/2022-03-01 | SICK
Subject to change without notice
O P E R A T I N G I N S T R U C T I O N S | safeRS3