Example 3
Both digital inputs have been linked to the dynamic configuration.
Dynamic
configuration
number
Input 1
Input 2
#1
0
0
#2
1
0
#3
0
1
#4
1
1
0 = signal deactivated; 1 = signal activated
4.7.5
Dynamic configuration through the safety Fieldbus
To activate the dynamic system configuration, connect an external safety PLC that
communicates through the safety Fieldbus to the control. This makes it possible to
dynamically switch between all the preset configurations, therefore up to 32 different
configurations. For all the parameters used for each configuration (see
).
For details about the supported protocol, please refer to the Fieldbus manual.
WARNING
Before activating the dynamic system configuration through the safety Fieldbus, ensure
it has not already been activated through the digital inputs. If the activation is set for
both the digital inputs and the safety Fieldbus, safeRS3 uses the digital input data and
ignores the dynamic changes made through the safety Fieldbus.
4.7.6
Safe configuration change
The change of the configuration takes place safely both on stationary and moving
machinery. The sensor always monitors the entire monitored area and when it receives
a request to change to a configuration with a longer protective field, it immediately
reverts to safe state if people are present in such a field.
4 GET TO KNOW SAFERS3
8027489/2022-03-01 | SICK
Subject to change without notice
O P E R A T I N G I N S T R U C T I O N S | safeRS3
35