Electrical Installation
ABOX with terminals and cable glands "MTA...-S02.-...-00"
Operating Instructions – MOVIFIT
®
SC
35
6.3
ABOX with terminals and cable glands "MTA...-S02.-...-00"
The following figure depicts the connection box with terminals and cable glands "MTA…-
S02.-…-00":
6.3.1
Additional installation instructions for "MTA...-S02.-...-00"
Permitted
connection
cross-section
and current
carrying capacity
of the terminals
Conductor end
sleeves
Use conductor end sleeves without insulating shrouds for terminals X1, X20, X8, and X9
(DIN 46228 part 1, material E-CU).
61095AXX
MTA...-S02.-...-00
Terminal data
X1 / X20
X8 / X9
X25 / X29 / X30 / X31 /
X35 / X45 / X81 / X91
Connection cross-
section (mm
2
)
0.2 mm
2
to 6 mm
2
0.08 mm
2
to 4
1)
mm
2
1) The maximum permitted cross-section is reduced by one unit when using conductor end sleeves
(e.g. 2.5 mm
2
Æ
1.5 mm
2
)
0.08 mm
2
to 2.5
1)
mm
2
Connection cross-
section (AWG)
AWG 24 to AWG 10
AWG 28 to AWG 12
1)
AWG 28 to AWG 14
1)
Current carrying
capacity (max.
continuous current)
X1: 32 A
X1: 16 A
20 A
10 A
Conductor stripping
length
13 mm to 15 mm
8 mm to 9 mm
5 mm to 6 mm