8
Operation
MOVIFIT® SC operating displays
Operating Instructions – MOVIFIT
®
SC
107
8.1.3
Bus-specific LEDs for PROFINET
This section describes the bus-specific LEDs for PROFINET. In the following figure, the
LEDs are shown as dark:
States of the
"RUN" LED
61122AXX
RUN PS
MOVIFIT
®
SF BF
24V
-C
24V
-S
RUN
link/act 1
link/act 2
DI03
DI01DI02
DI00
DI04DI05DI06DI07
DI08DI09DI10DI1
1
DI12/DO00
DI13/DO01
DI14/DO02
DI15/Do03
RUN
BF
SF
Function
level
Meaning
Troubleshooting
C
T
S
Green
x
x
• •
MOVIFIT
®
components
hardware OK
–
Green
Off
Off
• •
•
Correct MOVIFIT
®
operation
•
MOVIFIT
®
is currently
exchanging data with
the PROFINET master
(data exchange) and all
subordinate drive systems.
–
Off
x
x
• •
•
MOVIFIT
®
not ready for
operation
•
DC 24 V power supply is
not present.
•
Check DC 24 V
voltage
supply
•
Switch MOVIFIT
®
on
again. Exchange EBOX
if problem occurs
repeatedly.
Red
x
x
• •
Fault in MOVIFIT
®
components
hardware.
Switch MOVIFIT
®
on again.
Exchange EBOX if problem
occurs repeatedly.
Flashing
green
x
x
• •
MOVIFIT
®
components
hardware cannot start.
Switch MOVIFIT
®
on again.
Exchange EBOX if problem
occurs repeatedly.
Flashing
yellow
x
x
• •
MOVIFIT
®
components
hardware cannot start.
Switch MOVIFIT
®
on again.
Exchange EBOX if problem
occurs repeatedly.
Yellow
x
x
• •
MOVIFIT
®
components
hardware cannot start.
Switch MOVIFIT
®
on again.
Exchange EBOX if problem
occurs repeatedly.
X
•
Any state
Valid for selected function level:
C = Function level "Classic"
T = Function level "Technology"
S = Function level "System"
0
0
I
Summary of Contents for MOVIFIT SC series
Page 2: ...SEW EURODRIVE Driving the world ...
Page 146: ......