6
Electrical Installation
HanModular® ABOX "MTA...-H12.-...-00" and "MTA...-H22.-...-00"
74
Operating Instructions – MOVIFIT
®
SC
6.5.8
Assignment of M23 expansion plug connector X19 (alternative for standard I/Os)
The following figure depicts the M23 expansion plug connector (female) (alternative for
standard I/Os):
NOTES
The M23 expansion plug connector can only be used with the following function levels:
• "Technology" or "System" with PROFIBUS, DeviceNet or PROFINET
• "Classic" with PROFINET
60568AXX
No.
Pin
Name
Function
X19
1
DI01
Binary input DI01 (switching signal)
2
DI03
Binary input DI03 (switching signal)
3
DI05
Binary input DI05 (switching signal)
4
DI07
Binary input DI07 (switching signal)
5
DI09
Binary input DI09 (switching signal)
6
DI11
Binary input DI11 (switching signal)
7
DI13/DO01
Binary input DI13 or binary output DO01 (switching signal)
1)
1) Important: The reference potential is 0V24_S. When you use the inputs DI13 and DI15 or the outputs
DO01 and DO03 via the X19 expansion connector, the reference potentials 0V24_C and 0V24_S must be
connected with each other (e.g. via terminal X29).
8
DI15/DO03
Binary input DI15 or binary output DO03 (switching signal)
1)
9
0V24_C
0V24 reference potential for sensors
10
0V24_C
0V24 reference potential for sensors
11
V024-III
+24V sensor supply group III, from +24V_C
12
FE
Functional ground