6
Electrical Installation
Power bus connection examples
Operating Instructions – MOVIFIT
®
SC
81
6.6.2
Power bus in conjunction with HanModular
®
plug connector
Power
distribution and
cable protection
• It is recommended that you use HARTING Power S products for power bus project
planning.
• Two cables of max. 6 mm
2
can be routed in the AC 400 V 50/60 Hz and DC 24 V
supply cable.
• The spur lines that lead to the MOVIFIT
®
have a cross-section of 4 mm
2
and are a
maximum of 1.5 m long.
• Power S products are available from Harting with part number 61 04 202 1069.
NOTES
This example is valid for the following connection box:
• HanModular
®
ABOX "MTA...-H12.-...-00" and "MTA...-H22.-...-00"
60507AXX