4.2.2.3.
Installing the differential protection
The generating set is equipped with a residual current device in order to guarantee individuals are protected from electric shocks with
the TT system. This may be fixed ("vigi" unit) or adjustable (Resys) depending on the option chosen.
•
If the generating set's residual current device is fixed and the activation threshold is set to 30 mA, it is guaranteed to protect people.
•
If the generating set's residual current device is fixed and the activation threshold has been set at 300 mA, a 30mA residual current
device must be added to each of the circuit outlets in use.
•
If the generating set's residual current device is adjustable, (located upstream) this must be above those devices located
downstream (terminal circuits); this means that continuity on clean circuits will be maintained in the event of a fault on one of the
terminal circuits (see the following point on setting the residual current device).
Example:
Risk of electric shock
.
The generating set's differential relay is factory-set with a current threshold of 0.03 A (30 mA) and with an
automatic time delay (0 s).
Any change to the setting on the residual current device could pose a risk to personal safety. The user will be held
liable - any changes must only be made by trained, qualified engineers.
If the setting is modified, it is essential to restore the original settings after use.
Generating set's residual
current device
Residual current device
Terminal circuit 1
Residual current device
Terminal circuit 2
Residual current device
Terminal circuit 3
0.3A
(300mA)
0.03A
30mA
0.03A
30mA
0.03A
30mA
Generating set
40/242
Summary of Contents for R33C3
Page 2: ......
Page 94: ...92 242 ...
Page 95: ...10 Appendix 10 1 Appendix A Engine user and maintenance manual 93 242 ...
Page 96: ...94 242 ...
Page 98: ...96 242 ...
Page 115: ...113 242 ...
Page 135: ...133 242 ...
Page 145: ...143 242 ...
Page 179: ...177 242 ...
Page 191: ...July 2009 Pub No 99610 29120 OPERATION MAINTENANCE MANUAL 189 242 ...
Page 192: ...Printed in Japan Pub No 99610 29120 190 242 ...
Page 193: ...10 2 Appendix B Alternator user and maintenance manual 191 242 ...
Page 194: ...192 242 ...
Page 196: ...194 242 ...
Page 227: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 225 242 ...
Page 242: ...14 LEROY SOMER 2010 11 f Installation and maintenance R438 NOTES 3971 en 240 242 ...
Page 243: ...LEROY SOMER 15 2010 11 f Installation and maintenance R438 NOTES 3971 en 241 242 ...