11
InstallatIon and maIntenance
LSA 42.2 - 2 & 4 POLE
ALTERNATORS
3433 en - 2010.10 / g
LEROY-SOMER
4.4 - Mechanical defects
Fault
cause
Bearing
Excessive overheating of one or both
bearings (bearing temperature 80°C above
the ambient temperature) (With or without
abnormal bearing noise)
- If the bearing has turned blue or if the grease has turned black, change the
bearing.
- Bearing not fully locked (abnormal play in the bearing cage)
- End shields incorrectly aligned
Abnormal
temperature
Excessive overheating of alternator frame
(more than 40° C above the ambient
temperature)
- Air flow (inlet-outlet) partially clogged or hot air is being recycled from
the alternator or engine
- Alternator operating at too high a voltage (> 105% of Un on load)
- Alternator overloaded
Vibrations
Too much vibration
- Misalignment (coupling)
- Defective mounting or play in coupling
- Rotor balancing fault (Engine - Alternator)
Excessive vibration and humming noise
coming from the machine
- Phase imbalance
- Stator short-circuit
Abnormal noise
Alternator damaged by a significant impact,
followed by humming and vibration
- System short-circuit
- Misparalleling
Possible consequences
- Broken or damaged coupling
- Broken or bent shaft end
- Shifting and short-circuit of main field
- Fan fractured or coming loose on shaft
- Irreparable damage to rotating diodes/AVR
4.5 - Electrical faults
Fault
Action
Effect
Check/Cause
No voltage at no
load on start-up
Connect a new battery of
4 to 12 volts to terminals
E- and E+, respecting the
polarity, for 2 to 3 seconds
The alternator builds up and its voltage
is still correct when the battery is
removed.
- Lack of residual magnetism
The alternator builds up but its voltage
does not reach the rated value when
the battery is removed.
- Check the connection of the voltage reference to the
AVR
- Faulty diode
- Armature short-circuit
The alternator builds up but its voltage
disappears when the battery is
removed.
- Faulty AVR
- Field windings open circuit (check winding)
- Main field winding open circuit (check the resistance)
Voltage too low Check the drive speed
Correct speed
Check the AVR connections (possible AVR failure)
- Field windings short-circuited
- Rotating diodes burnt out
- Main field winding short-circuited - Check the
resistance
Speed too low
Increase the drive speed
(Do not touch the AVR voltage pot. (P2) before running
at the correct speed.)
Voltage too high Adjust AVR voltage
potentiometer
Adjustment ineffective
Faulty AVR
Voltage
oscillations
Adjust AVR stability
potentiometer
If no effect : try normal / fast recovery
modes (ST2)
- Check the speed : possibility of cyclic irregularity
- Loose connections
- Faulty AVR
- Speed too low when on load (or LAM set too high)
Voltage correct
at no load and
too low when on
load (*)
Run at no load and check
the voltage between E+ et
E- on the AVR
Voltage between E+ and E–
SHUNT < 6V - AREP < 10V
- Check the speed (or LAM set too high)
Voltage between E+ and E–
SHUNT > 10V - AREP > 15V
- Faulty rotating diodes
- Short-circuit in the main field. Check the resistance.
- Faulty exciter armature. Check the resistance.
(*) Warning :
During single-phase operation, check that the sensing wires from the AVR are connected to the correct output terminals.
Voltage
disappears
during operation
Check the AVR, the surge
suppressor, the rotating
diodes, and replace any
defective components
The voltage does not return to the rated
value.
- Exciter winding open circuit
- Faulty exciter armature
- Faulty AVR
- Main field open circuit or short-circuited
(**) Warning :
The AVR internal protection may cut in (overload lost connection, short circuit).
205/242
Summary of Contents for R33C3
Page 2: ......
Page 94: ...92 242 ...
Page 95: ...10 Appendix 10 1 Appendix A Engine user and maintenance manual 93 242 ...
Page 96: ...94 242 ...
Page 98: ...96 242 ...
Page 115: ...113 242 ...
Page 135: ...133 242 ...
Page 145: ...143 242 ...
Page 179: ...177 242 ...
Page 191: ...July 2009 Pub No 99610 29120 OPERATION MAINTENANCE MANUAL 189 242 ...
Page 192: ...Printed in Japan Pub No 99610 29120 190 242 ...
Page 193: ...10 2 Appendix B Alternator user and maintenance manual 191 242 ...
Page 194: ...192 242 ...
Page 196: ...194 242 ...
Page 227: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 225 242 ...
Page 242: ...14 LEROY SOMER 2010 11 f Installation and maintenance R438 NOTES 3971 en 240 242 ...
Page 243: ...LEROY SOMER 15 2010 11 f Installation and maintenance R438 NOTES 3971 en 241 242 ...