Installation and maintenance
R250
A.V.R.
8
LEROY-SOMER
4067 en - 2009.05 / b
3 - INSTALLATION -
COMMISSIONING
3.1 - Electrical checks on the AVR
- Check that all connections have been
made properly as shown in the attached
wiring diagram.
- Check that the position of the jumper
corresponds to the operating frequency.
- Check whether the ST4 jumper or the
remote adjustment potentiometer have
been connected.
3.2 - Settings
The different settings made during the
trial are to be done by qualified personnel.
Respecting the load speed specified on
the nameplate is vital in order to start a
settings procedure. After operational
testing, replace all access panels or
covers.
The only possible settings on the
machine are to be done with the A.V.R.
3.2.1 - R250 settings (SHUNT system)
Initial potentiometer positions
- voltage setting potentiometer
P1
for the
A.V.R.: full left
- remote voltage setting potentiometer: in
the middle.
Operate the alternator at its rated speed: if
the voltage does not rise it is necessary to
re-magnatise the magnetic circuit.
- slowly adjust the voltage potentiometer of
the A.V.R.
P1
until the output voltage reaches
its rated value.
- Stability setting with
P2
.
3.2.2 - Special type of use
Excitation circuit E+, E- must not be left
open when the machine is running:
A.V.R. damage will occur.
3.2.2.1 - R250 field weakening (SHUNT)
The exciter is switched off by disconnecting
the A.V.R. power supply (1 wire - 0 or 110V).
Contact rating: 16A - 250V AC
Do not reclose the power supply until the
voltage has reached a value ≤15% of the
rated voltage (approximately 5 seconds
after opening)
3.2.2.2 - R250
field forcing
The battery must be isolated from the
mass.
Exciter field may be at line potential.
WARNING
E+ E-
0V
110
Battery (B Volt)
+
-
t
(400V - 10A)
Excitation Inducer
Diode
E+ E-
0V
110
222/242
Summary of Contents for R33C3
Page 2: ......
Page 94: ...92 242 ...
Page 95: ...10 Appendix 10 1 Appendix A Engine user and maintenance manual 93 242 ...
Page 96: ...94 242 ...
Page 98: ...96 242 ...
Page 115: ...113 242 ...
Page 135: ...133 242 ...
Page 145: ...143 242 ...
Page 179: ...177 242 ...
Page 191: ...July 2009 Pub No 99610 29120 OPERATION MAINTENANCE MANUAL 189 242 ...
Page 192: ...Printed in Japan Pub No 99610 29120 190 242 ...
Page 193: ...10 2 Appendix B Alternator user and maintenance manual 191 242 ...
Page 194: ...192 242 ...
Page 196: ...194 242 ...
Page 227: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 225 242 ...
Page 242: ...14 LEROY SOMER 2010 11 f Installation and maintenance R438 NOTES 3971 en 240 242 ...
Page 243: ...LEROY SOMER 15 2010 11 f Installation and maintenance R438 NOTES 3971 en 241 242 ...