Installation and maintenance
R438
A.V.R.
2 - R438 A.V.R.
2.1 - Characteristics
- Storage : -55°C ; +85°C
- Operation : -40°C ; +70°C
- Standard power supply: AREP or PMG.
- Rated overload current: 8 A - 10 s
- Electronic protection (overload, short-cir-
cuit on opening of voltage sensing circuit):
excitation overload current for 10 seconds
then return to approximately 1A. The alter-
nator must be stopped (or the power
switched off) in order to reset the protection.
- Fuse : F1 on X1, X2. 8A ; slow - 250V
- Voltage sensing : 5 VA isolated via trans-
former ;
• 0-110 V terminals = 95 to 140 V,
• 0-220 V terminals = 170 to 260 V,
• 0-380 V terminals = 340 to 520 V.
- Voltage regulation ± 1%.
- Normal or rapid response time via
ST2
jumper (see below).
- Voltage adjustment via potentiometer
P2
.
other voltages via adapter transformer
- Current sensing (parallel operation): C.T.
2.5 VA cl1, secondary 1 A (optional).
- Quadrature droop adjustment via potentio-
meter
P1
.
- Max. excitation current adjustment via
P5
(see below).
2.1.1 -
Configuration jumpers function
Pot.
Delivrery
config.
Position
Function
Open Closed
ST1
3-ph.
Mono
Open for module
installation tri detection
ST2
Fast
Normal
Response time
ST3
50 ou 60 Hz Frequency selection
ST4
External
potentio-
meter
Without
Potentiometer
ST5 Without
With
LAM
ST9 Others
(PMG...) AREP
Supply
ST10
13% or 25% LAM voltage drop
amplitude
ST11 65 Hz
48 or
58 Hz
U/f function bend
position
2.1.2 -
Setting potentiometers
function
Delivrery
position
Pot.
Function
0
P1 Quadrature droop ; // operation with C.T.
400V
P2 Voltage
Centre
P3 Stability
Maxi
P5 Excitation current ceiling
2.2 - Frequency compared with
voltage (without LAM)
2.3 - LAM (Load Acceptance
Module) characteristics
2.3.1 - Voltage drop
The LAM system is integrated in the R 438
AVR as standard.
Role of the «LAM» (Load Adjustment Mo-
dule) :
On application of a load, the rotation speed
of the generator set decreases. When it
passes below the preset frequency thres-
hold, the LAM causes the voltage to drop by
approximately 13% or 25% and conse-
quently the amount of active load applied is
reduced by approximately 25% to 50%, until
the speed reaches its rated value again.
Hence the LAM can be used either to reduce
the speed variation (frequency) and its dura-
tion for a given applied load, or to increase
the applied load possible for one speed va-
riation (turbo-charged engine).
To avoid voltage oscillations, the trip thres-
hold for the LAM function should be set ap-
proximately 2 Hz below the lowest frequen-
cy in steady state.
100 %
50 Hz
60 Hz
Hz
50 Hz
48 Hz
57.5 Hz
60 Hz
Voltage
Bend
U/U
N
Frequency
3971 en -
232/242
Summary of Contents for R33C3
Page 2: ......
Page 94: ...92 242 ...
Page 95: ...10 Appendix 10 1 Appendix A Engine user and maintenance manual 93 242 ...
Page 96: ...94 242 ...
Page 98: ...96 242 ...
Page 115: ...113 242 ...
Page 135: ...133 242 ...
Page 145: ...143 242 ...
Page 179: ...177 242 ...
Page 191: ...July 2009 Pub No 99610 29120 OPERATION MAINTENANCE MANUAL 189 242 ...
Page 192: ...Printed in Japan Pub No 99610 29120 190 242 ...
Page 193: ...10 2 Appendix B Alternator user and maintenance manual 191 242 ...
Page 194: ...192 242 ...
Page 196: ...194 242 ...
Page 227: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 225 242 ...
Page 242: ...14 LEROY SOMER 2010 11 f Installation and maintenance R438 NOTES 3971 en 240 242 ...
Page 243: ...LEROY SOMER 15 2010 11 f Installation and maintenance R438 NOTES 3971 en 241 242 ...