4.2.2.4.
Setting the generating set differential protection
The setting of the generating set's residual current device is guaranteed by a differential relay fitted near the control unit (type A / AC or
B depending on the generating sets). As a result, two parameters relating to the downstream device (terminal circuit) must be set:
-
Current threshold: the generating set's differential relay must be three times more sensitive than that of the terminal circuit.
-
Time delay: the cut-off of the generating set's differential relay must be longer than that of the terminal circuit.
-
Type A / AC differential relay
:
Use:
Differential relay for which operation is guaranteed:
•
for residual sinusoidal alternating currents;
•
for continuous pulsed residual currents;
•
for continuous pulsed residual currents with a continuous component of 0.006 A with or without phase check,
independent of the polarity.
Setting:
1. Use a screwdriver to set the current
threshold potentiometer (1) to 0.03 A (30
mA).
2.
Use a screwdriver to set the time delay
potentiometer (2) to 0s (automatic).
3. Test
the
residual
current device using the
"Test" button on the relay (3).
Current threshold potentiometer
(1)
Time setting potentiometer
(2)
Test Button
(3)
41/242
Summary of Contents for R33C3
Page 2: ......
Page 94: ...92 242 ...
Page 95: ...10 Appendix 10 1 Appendix A Engine user and maintenance manual 93 242 ...
Page 96: ...94 242 ...
Page 98: ...96 242 ...
Page 115: ...113 242 ...
Page 135: ...133 242 ...
Page 145: ...143 242 ...
Page 179: ...177 242 ...
Page 191: ...July 2009 Pub No 99610 29120 OPERATION MAINTENANCE MANUAL 189 242 ...
Page 192: ...Printed in Japan Pub No 99610 29120 190 242 ...
Page 193: ...10 2 Appendix B Alternator user and maintenance manual 191 242 ...
Page 194: ...192 242 ...
Page 196: ...194 242 ...
Page 227: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 225 242 ...
Page 242: ...14 LEROY SOMER 2010 11 f Installation and maintenance R438 NOTES 3971 en 240 242 ...
Page 243: ...LEROY SOMER 15 2010 11 f Installation and maintenance R438 NOTES 3971 en 241 242 ...