Installation and maintenance
R438
A.V.R.
The best response times are obtained at the
limit of the instability. If no stable position
can be obtained, try disconnecting or repla-
cing the ST2 jumper (normal/fast).
h
) Check LAM operation :
ST5
closed.
i)
Vary the frequency (speed) around 48 or
58 Hz according to the operating frequency,
and check the change in voltage from that
observed previously (~ 15%).
j
) Readjust the speed of the unit to its rated
no-load value.
Adjustments in parallel operation
Before any intervention on the alterna-
tor, make sure that the speed droop is
identical for all engines
.
k
) Preset for parallel operation (with C.T.
connected to S1, S2)
- Potentiometer P1 (quadrature droop) in
centre position.
Apply the rated load (cos
ϕ
= 0.8 inductive).
The voltage should drop by 2 to 3%. If it in-
creases, check that V and W and also S1
and S2 have not been reversed.
l
) The no-load voltages should be identical
for all the alternators intended to run in pa-
rallel.
- Couple the machines in parallel.
- By adjusting the
speed
, try to obtain
0 KW
power exchange.
- By altering the voltage setting P2 on one of
the machines, try to cancel (or minimise)
the
current
circulating between the machines.
- From now on, do not touch the voltage set-
tings.
m
) Apply the available load (the setting is only
correct if a
reactive
load is available)
- By altering the
speed
, match the
kW
(or di-
vide the rated power of the units proportionally)
- By altering the quadrature droop potentiome-
ter
P1
, match or divide the
currents
.
3.2.2 - Max. excitation setting (excitation
ceiling)
Static adjustment of the current limit,
potentiometer P5 (factory setting: 7.5 A,
fuse rating: 8 A - 10 seconds).
The maximum factory setting corresponds
to that of the excitation current required to
obtain a 3-phase short-circuit current of
approximately 3 IN at 50 Hz for industrial
power, unless otherwise specified(*).
A static method can be used to reduce this
value or adapt the Isc to the actual operating
power (derated machine), which is safer for
the alternator and the installation.
Disconnect power supply wires X1,X2 and
Z1,Z2 and the voltage reference
(0-110V-220V-380V) on the alternator.
Connect the mains power supply using a
transformer (200-240V) as indicated
(X1,X2 : 48V). Install a 10A D.C. ammeter
in series with the exciter field. Turn P5 fully
anti-clockwise and activate the power
supply. If there is no output current from the
AVR, turn potentiometer P2 (voltage)
clockwise until the ammeter indicates a
stable current. Switch the power supply off,
then on again, turn P5 clockwise until the
required max. current is obtained (no more
than 8 A).
Depending on
the mains frequency
Main
(50/60 Hz supply)
Max. excitation
Voltage
Field
~ 5 ohms
X2
Z1
X1
Z2
E+
E-
0V
110 V
220 V
380 V
50Hz 60Hz
P2
P3
P5
ST3
10 A CC/DC
48 V
110/220/380 V
R 438
ST4
A
+
–
A
D
3971 en -
236/242
Summary of Contents for R33C3
Page 2: ......
Page 94: ...92 242 ...
Page 95: ...10 Appendix 10 1 Appendix A Engine user and maintenance manual 93 242 ...
Page 96: ...94 242 ...
Page 98: ...96 242 ...
Page 115: ...113 242 ...
Page 135: ...133 242 ...
Page 145: ...143 242 ...
Page 179: ...177 242 ...
Page 191: ...July 2009 Pub No 99610 29120 OPERATION MAINTENANCE MANUAL 189 242 ...
Page 192: ...Printed in Japan Pub No 99610 29120 190 242 ...
Page 193: ...10 2 Appendix B Alternator user and maintenance manual 191 242 ...
Page 194: ...192 242 ...
Page 196: ...194 242 ...
Page 227: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 225 242 ...
Page 242: ...14 LEROY SOMER 2010 11 f Installation and maintenance R438 NOTES 3971 en 240 242 ...
Page 243: ...LEROY SOMER 15 2010 11 f Installation and maintenance R438 NOTES 3971 en 241 242 ...