- LAM : action eliminated by cutting the ST5
jumper.
2.3.2 - Gradual voltage return function
During load impacts, the function helps the
genset to return to its rated speed faster
thanks to a gradual increase in voltage ac-
cording to the principle:
- If the speed drops between 46 and 50 Hz,
the rated voltage follows a fast gradient as it
is restored.
- If the speed drops below 46 Hz, since the
engine needs more help, the voltage follows
a slow gradient as it returns to the reference
value.
2.4 - Typical effects of the LAM with
a diesel engine with or without a
LAM (U/F only)
2.4.1 - Voltage
2.4.2 - Frequency
2.4.3 - Power
LAM
U
N
0
48 or 57.5 Hz
0.85 U
N
Voltage
U/f
50 or 60 Hz
fC
fN
Voltage
ST5 disconnected
ST3
P2
Underspeed and LAM
0
Time
Drop N
≤
46 Hz
U
Drop N > 46 Hz
U
N
0
0,9
0,8
(U/f)
with
LAM
Time
without LAM
1 s
2 s
3 s
Transient voltage drop
0,9
0,8
f
N
Max speed drop
0
with
LAM
Time
without
LAM
1 s
2 s
3 s
0
1 s
2 s
3 s
Time
LAM
Variation in the load
Load on the shaft (kW)
Load shedding due to "LAM"
3971 en -
233/242
Summary of Contents for R33C3
Page 2: ......
Page 94: ...92 242 ...
Page 95: ...10 Appendix 10 1 Appendix A Engine user and maintenance manual 93 242 ...
Page 96: ...94 242 ...
Page 98: ...96 242 ...
Page 115: ...113 242 ...
Page 135: ...133 242 ...
Page 145: ...143 242 ...
Page 179: ...177 242 ...
Page 191: ...July 2009 Pub No 99610 29120 OPERATION MAINTENANCE MANUAL 189 242 ...
Page 192: ...Printed in Japan Pub No 99610 29120 190 242 ...
Page 193: ...10 2 Appendix B Alternator user and maintenance manual 191 242 ...
Page 194: ...192 242 ...
Page 196: ...194 242 ...
Page 227: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 225 242 ...
Page 242: ...14 LEROY SOMER 2010 11 f Installation and maintenance R438 NOTES 3971 en 240 242 ...
Page 243: ...LEROY SOMER 15 2010 11 f Installation and maintenance R438 NOTES 3971 en 241 242 ...