List of faults which will cause the generating set to stop and generate a fault code
Low coolant level fault: indicates that the level of coolant is
low in the radiator (linked to a two second time delay).
Or
Overload or short-circuit fault (optional): with the circuit
breaker SD contact closing (overload or short-circuit), the
generating set switches off immediately also causing the
main circuit breaker to be triggered.
Associated message
Additional fault linked to message opposite: is displayed in
the following two cases:
Differential fault (1)
insulation
fault
(2)
(1) Differential fault (optional): with a differential fault
causing the activation of the differential relay, the
generating set stops immediately also causing the
main circuit breaker to be tripped.
(2) Insulation fault (optional): with an insulation fault
causing the activation of the control unit performing
insulation, the generating set stops immediately.
Associated message
Underspeed fault: indicates an incorrect rotation speed
(below 1000 rpm).
Associated message
Emergency stop or external emergency stop fault
Associated message
"STOP" fault activated if the "STOP" button is pressed
whilst the "AUT" LED is flashing to indicate that the
generating set is operating in automatic mode.
Associated message
List of alarms associated with a pictogram
Low fuel level alarm: Indicates the need to fill up with fuel.
Associated pictogram
"Alternator charging fault" alarm indicates a problem
affecting the alternator charging rate.
Associated pictogram
57/242
Summary of Contents for R33C3
Page 2: ......
Page 94: ...92 242 ...
Page 95: ...10 Appendix 10 1 Appendix A Engine user and maintenance manual 93 242 ...
Page 96: ...94 242 ...
Page 98: ...96 242 ...
Page 115: ...113 242 ...
Page 135: ...133 242 ...
Page 145: ...143 242 ...
Page 179: ...177 242 ...
Page 191: ...July 2009 Pub No 99610 29120 OPERATION MAINTENANCE MANUAL 189 242 ...
Page 192: ...Printed in Japan Pub No 99610 29120 190 242 ...
Page 193: ...10 2 Appendix B Alternator user and maintenance manual 191 242 ...
Page 194: ...192 242 ...
Page 196: ...194 242 ...
Page 227: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 225 242 ...
Page 242: ...14 LEROY SOMER 2010 11 f Installation and maintenance R438 NOTES 3971 en 240 242 ...
Page 243: ...LEROY SOMER 15 2010 11 f Installation and maintenance R438 NOTES 3971 en 241 242 ...