As not all the settings are available, go to the "37
INSTALLER ACCESS" menu to enter the code "1966"
using the knob to call up the desired menus.
INSTALLER ACCESS
Enter
password
*
* * *
12
OK Esc
•
Using the knob, select "34 50Hz<>60Hz" and press the
knob to confirm.
•
Select and confirm the desired frequency using the
knob to scroll and confirm (50 Hz or 60 Hz).
•
Return to the "3 SETTINGS" screen and use the knob
to select "35 NOMINAL VOLTAGE" then press the
knob to confirm.
•
Set the desired voltage then confirm using the scroll
and confirm knob.
NOMINAL VOLTAGE
400
Vac
Min.: 380
Max.:
480
12
OK Esc
3 SETTINGS
2/2
31 COMMUNICATION
32 FREQUENCY
33 VOLTAGE
34 50Hz <> 60Hz
12
OK Esc
50Hz <> 60Hz
50Hz
12
OK Esc
3 SETTINGS
4/7
34 50Hz <> 60Hz
35 NOMINAL VOLTAGE
36 PARAMETERS
37 INSTALLER ACCESS
12
OK Esc
3 SETTINGS
4/7
34 50Hz <> 60Hz
35 NOMINAL VOLTAGE
36 PARAMETERS
37 INSTALLER ACCESS
12
OK Esc
89/242
Summary of Contents for R33C3
Page 2: ......
Page 94: ...92 242 ...
Page 95: ...10 Appendix 10 1 Appendix A Engine user and maintenance manual 93 242 ...
Page 96: ...94 242 ...
Page 98: ...96 242 ...
Page 115: ...113 242 ...
Page 135: ...133 242 ...
Page 145: ...143 242 ...
Page 179: ...177 242 ...
Page 191: ...July 2009 Pub No 99610 29120 OPERATION MAINTENANCE MANUAL 189 242 ...
Page 192: ...Printed in Japan Pub No 99610 29120 190 242 ...
Page 193: ...10 2 Appendix B Alternator user and maintenance manual 191 242 ...
Page 194: ...192 242 ...
Page 196: ...194 242 ...
Page 227: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 225 242 ...
Page 242: ...14 LEROY SOMER 2010 11 f Installation and maintenance R438 NOTES 3971 en 240 242 ...
Page 243: ...LEROY SOMER 15 2010 11 f Installation and maintenance R438 NOTES 3971 en 241 242 ...