4.2.
Connecting the generating set
4.2.1
Connection summary
This diagram can be used to retrace the different steps enabling the generating set to be correctly connected.
TT earthing system
TT
"EDF application" option (France
only)
Identify the type of differential protection
fitted on the generating set
Fixed differential protection
Adjustable differential protection
Set the differential protection
of the generating set
30 mA
30 mA
300 mA
300 mA
No operation required:
terminal circuits protected
No operation required:
terminal circuits protected
Add differential protection
set to 30 mA to the terminal
circuit output(s)
Add differential protection
set to 30 mA to the terminal
circuit output(s)
Earth the generating set
Connect the generating set to the installation
38/242
Summary of Contents for R33C3
Page 2: ......
Page 94: ...92 242 ...
Page 95: ...10 Appendix 10 1 Appendix A Engine user and maintenance manual 93 242 ...
Page 96: ...94 242 ...
Page 98: ...96 242 ...
Page 115: ...113 242 ...
Page 135: ...133 242 ...
Page 145: ...143 242 ...
Page 179: ...177 242 ...
Page 191: ...July 2009 Pub No 99610 29120 OPERATION MAINTENANCE MANUAL 189 242 ...
Page 192: ...Printed in Japan Pub No 99610 29120 190 242 ...
Page 193: ...10 2 Appendix B Alternator user and maintenance manual 191 242 ...
Page 194: ...192 242 ...
Page 196: ...194 242 ...
Page 227: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 225 242 ...
Page 242: ...14 LEROY SOMER 2010 11 f Installation and maintenance R438 NOTES 3971 en 240 242 ...
Page 243: ...LEROY SOMER 15 2010 11 f Installation and maintenance R438 NOTES 3971 en 241 242 ...