Installation and maintenance
R250
A.V.R.
4067 en - 2009.05 / b
LEROY-SOMER
9
3.3 - Electrical faults
Warning: after setting-up or trouble-
shooting, replace all access panels or
covers.
Fault
Action
Effect
Check/cause
No voltage at
no load on
start-up
Connect a new battery
of 4 to 12 volts to
terminals E- and E+
respecting the polarity
for 2 to 3 seconds
The alternator starts up and its
voltage is still correct when the
battery is removed.
- Lack of residual magnetism
The alternator starts up but its
voltage does not reach the rated
value when the battery is
removed.
- Check the connection of the voltage
reference to the A.V.R.
- Faulty diodes
- Induced short circuit
The alternator starts up but its
voltage disappears when the
battery is removed
- Faulty A.V.R.
- Exciter field short-circuited
- Short-circuit in the main field. Check the
resistance
Voltage too
low
Check the drive speed
Correct speed
Check the A.V.R. connections (A.V.R. may
be faulty)
- Field windings short-circuited
- Rotating diodes burnt out
- Main field winding short-circuited
- Check the resistance
Speed too low
Increase the drive speed
(Do not touch the A.V.R. pot (P1) before
returning to the correct speed.)
Voltage too
high
Adjust A.V.R.
potentiometer
Adjustment ineffective
- Faulty A.V.R.
- 1 faulty diode
Voltage
oscillations
Adjust A.V.R. stability
potentiometer
- Check the speed: possibility of cyclic
irregularity
- Loose terminals
- Faulty A.V.R.
- Speed too low on load
(or U/F gradient set too high)
Voltage
correct at no
load and too
low when on
load (*)
Run at no load and
check the voltage
between E+ and E- on
the A.V.R.
- Check the speed (or U/F gradient set too
high)
- Faulty rotating diodes
- Short-circuit in the main field. Check the
resistance
- Faulty induced excitaion
(*) Warning:
For single-phase operation, check that the sensing wires coming from the A.V.R. are correctly connected to
the operating terminals (see the alternator manual).
Voltage
disappears
during
operation
Check the A.V.R., the
surge suppressor, the
rotating diodes and
replace any defective
components
The voltage does not return to the
rated value
- Exciter winding open circuit
- Faulty induced excitation
- Faulty A.V.R.
- Main field open circuit or short-circuited
223/242
Summary of Contents for R33C3
Page 2: ......
Page 94: ...92 242 ...
Page 95: ...10 Appendix 10 1 Appendix A Engine user and maintenance manual 93 242 ...
Page 96: ...94 242 ...
Page 98: ...96 242 ...
Page 115: ...113 242 ...
Page 135: ...133 242 ...
Page 145: ...143 242 ...
Page 179: ...177 242 ...
Page 191: ...July 2009 Pub No 99610 29120 OPERATION MAINTENANCE MANUAL 189 242 ...
Page 192: ...Printed in Japan Pub No 99610 29120 190 242 ...
Page 193: ...10 2 Appendix B Alternator user and maintenance manual 191 242 ...
Page 194: ...192 242 ...
Page 196: ...194 242 ...
Page 227: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 225 242 ...
Page 242: ...14 LEROY SOMER 2010 11 f Installation and maintenance R438 NOTES 3971 en 240 242 ...
Page 243: ...LEROY SOMER 15 2010 11 f Installation and maintenance R438 NOTES 3971 en 241 242 ...