3. Check the length of the earthing rod depending on the
nature of the ground and adapt if necessary.
The equipment supplied is not suitable for
bare stony soils, dry sand or impermeable
rock.
IMPORTANT
Nature of ground
Length of earthing
rod (in metres)
Thick arable land, damp
compact backfill
1
Thin arable land, gravel, rough
backfill
1
Bare stony soils, dry sand,
impermeable rock
4 or 4 x 1
4.
Plant the earthing rod in the ground and connect it to the
earth cable.
Note: For the United States (National Electrical Code ref. NFPA-70), use a copper wire with a minimum cross-section of 13.3 mm² (or
AWG 6 at most) connected to the generating set's earth connection and a galvanised steel earthing rod completely buried in the ground
in an upright position. This earthing rod must be at least 2.5 m long (of which at least 1 m must be in the ground).
4.2.3
Making the connections
4.2.3.1.
Connections - general information
When connecting, always comply with standard NFC 15-100 and the application guide NFC 15-401 (in France) or follow standards
based on the international standard IEC 60364 (countries outside France).
The cable cross-section and number of connection cables should be determined according to the type of connection cable and the
current standards to be observed in the country of installation. The choice of connection cables must comply with international standard
IEC 60364-5-52.
1 meter
ground
Earth cable
44/242
Summary of Contents for R33C3
Page 2: ......
Page 94: ...92 242 ...
Page 95: ...10 Appendix 10 1 Appendix A Engine user and maintenance manual 93 242 ...
Page 96: ...94 242 ...
Page 98: ...96 242 ...
Page 115: ...113 242 ...
Page 135: ...133 242 ...
Page 145: ...143 242 ...
Page 179: ...177 242 ...
Page 191: ...July 2009 Pub No 99610 29120 OPERATION MAINTENANCE MANUAL 189 242 ...
Page 192: ...Printed in Japan Pub No 99610 29120 190 242 ...
Page 193: ...10 2 Appendix B Alternator user and maintenance manual 191 242 ...
Page 194: ...192 242 ...
Page 196: ...194 242 ...
Page 227: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 225 242 ...
Page 242: ...14 LEROY SOMER 2010 11 f Installation and maintenance R438 NOTES 3971 en 240 242 ...
Page 243: ...LEROY SOMER 15 2010 11 f Installation and maintenance R438 NOTES 3971 en 241 242 ...