![Savch S3100E Series User Manual Download Page 96](http://html.mh-extra.com/html/savch/s3100e-series/s3100e-series_user-manual_1203759096.webp)
92
Setting
value
Function
Description
39
Reserved
Reserved
40
Current running time reached
When the inverter's current running time exceeds the time set in
09-53, it outputs an ON signal.
06-05
DFM terminal output mode selection
Factory setting
0
Setting range
0
Pulse output(DFM(P))
1
Switch output(DFM(M))
The DFM terminal is a programmable multiplex terminal, which can be used as a high-speed pulse output
terminal (DFM(P)) or an open collector switching output terminal (DFM(M)).
When DFM(P) is output as a pulse, please refer to 06-06 for DFM(P) related functions. The maximum frequency
of the output pulse is 100kHz.
When DFM(M) is output as a switch, please refer to 06-04 for DFM(M) related functions.
06-06
DFM(P) output function selection
Factory setting
0
06-07
AFM output function selection
Factory setting
0
06-08
Reserved
Factory setting
DFM (P) terminal output pulse frequency range is 0.01kHz ~ 06-09 (DFM (P) output maximum frequency), 06-09
can be set between 0.01kHz ~ 100.00kHz.
Analog output AFM output range is 0V ~ 10V. The relationship between the range of pulse output or analog output
and the scaling of corresponding functions is shown in the following table:
Setting value Funtion
Pulse or analog output 0.0%~100.0% corresponding function
0
Running frequency
0 to max output frequency
1
Set frequency
0 to max output frequency
2
Output current
0 to 2 times of motor rated current
3
Output torque
0 to 2 times of motor rated torque
4
Output power
0 to 2 times rated power
5
Output voltage
0 to 1.2 times of inverter rated voltage
6
PULSE input
0.01kHz
~
100.00kHz
7
AVI1
0V
~
10V
8
AVI2/ACI
0V
~
10V(or 0
~
20mA)
9
Reserved
10
Length
0 to maximum set length
11
Count value
0 to maximum count value
12
Communication setting
0.0%
~
100.0%
13
Motor rotation speed
0
~
The rotation speed corresponding to maximum output
frequency
14
Output current
0.0A~1000.0A
15
BUS voltage
0.0V~1000.0V
Summary of Contents for S3100E Series
Page 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Page 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...