![Savch S3100E Series User Manual Download Page 102](http://html.mh-extra.com/html/savch/s3100e-series/s3100e-series_user-manual_1203759102.webp)
98
08-02
STOP/RESET key funciton
Factory setting
1
Setting range
0
Only in the keyboard operation mode, the STOP/RESET key stop function
is effective
1
In any operation mode, the STOP/RESET key stop function is effective
08-03
LED operation display parameter 1
Factory setting
1F
Setting range
0000
~
FFFF
Bit00
Running frequency1(Hz)
Bit01
Setting frequency(Hz)
Bit02
BUS Voltage(V)
Bit03
Output voltage(V)
Bit04
Output current(A)
Bit05
Output power(kW)
Bit06
Output torque(%)
Bit07
MI input status
Bit08
MO output status
Bit09
AVI1 voltage(V)
Bit10
AVI2/ACI voltage(V)
Bit11
Reserved
Bit12
Count value
Bit13
Length
Bit14
Load speed
Bit15
PID setting
If the above parameters need to be displayed during operation, set the
corresponding position to 1, set the binary number to hexadecimal and set it to
08-03.
08-04
LED operation display parameter 2
Factory setting
0
Setting range
0000
~
FFFF
Bit00
PID feedback
Bit01
PLC stage
Bit02
PULSE input pulse frequency(kHz)
Bit03
Running frequency 2(Hz)
Bit04
Remaining running time
Bit05
AVI1 voltage Before correction(V)
Bit06
AVI2/ACI voltage Before correction(V)
Bit07
Reserved
Bit08
Line speed
Bit09
Current power-on time(Hour)
Bit10
Current running time(Min)
Summary of Contents for S3100E Series
Page 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Page 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...