![Savch S3100E Series User Manual Download Page 37](http://html.mh-extra.com/html/savch/s3100e-series/s3100e-series_user-manual_1203759037.webp)
33
4 FUNCTIONAL PARAMETERS LIST
00 Basic functions parameters
indicates that the parameters can be set during operation
Parame
ter
Parameter function
Setting range
Factory
setting
00-00
Command source selection
1:Keyboard command (LED off)
2:Terminal command (LED on)
3:Communication command (LED flicker)
0
00-01
Keyboard and terminal UP /
DOWN setting selection
0:Stop memory and power failure storage
1:Stop memory
2:Stop no memory
2
00-02
Main
Frequency source
selection
0:Digital setting (keyboard given frequency
00-06, UP /DOWN can be modified)
1:AVI1
2:AVI2 / ACI
3:Reserved
4:Multi-speed command
5:PID control
6:Communication setting
7:Simple PLC
8:
Panel potentiometer
9:Pulse setting (MI5)
1
00-03
Maximum frequency
50.00Hz
~
500.00Hz
50.00Hz
00-04
Upper limitation of running
frequency
Lower limit frequency 00-05
~
max
frequency 00-03
50.00Hz
00-05
Lower limitation of running
frequency
0.00Hz
~
Upper limit frequency
0.00Hz
00-06
Keyboard setting frequency
0.00Hz to the maximum frequency (00-03)
50.00Hz
00-07
Acceleration time 1
0.00s
~
65000s
Type setting
00-08
Deceleration time 1
0.00s
~
65000s
Type setting
00-09
Operation direction
0: Reverse
1: Forward
1
00-10
Carrier frequency
0.5kHz
~
12.0kHz
Type setting
00-11
Parameter initialization
0:No operation
1:Restore factory parameters, excluding
motor parameters
2:Clear record information
0
00-12
Carrier frequency adjusts with
temperature
0:no
1:yes
1
00-13
G/P setting
1:G type (constant torque load model)
2:P type (fan, pump type)
1
00-14
Auxiliary frequency source Y
selection
Same as 00-02 (Main frequency source X
selection)
0
00-15
Auxiliary frequency source Y
range selection during
superposition
0:Relative to the maximum frequency
1:Relative to frequency source X
0
00-16
Auxiliary frequency source Y
range when superimposed
0%
~
150%
100%
Summary of Contents for S3100E Series
Page 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Page 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...