![Savch S3100E Series User Manual Download Page 111](http://html.mh-extra.com/html/savch/s3100e-series/s3100e-series_user-manual_1203759111.webp)
107
Output current
Time
Zero current
detection level
09-34
Zero current
detection signal
Time
ON
Zero current detection delay time 09-35
Figure 5-22 Schematic diagram of zero current detection
09-36
Output current limit
Factory setting
200.0%
Setting range
0.0%(No detection)
0.1%
~
300.0%(motor rated current)
09-37
Output overcurrent detection delay time
Factory setting
0.00s
Setting range
0.00s
~
600.00s
When the output current of the inverter is greater than or exceeds the limit detection point and the duration
exceeds the software overcurrent detection delay time, the inverter's multi-function output terminal (function 36)
outputs an ON signal. Figure 5-23 is a schematic diagram of the output overcurrent detection.
Output current
Time
Output current limit
09-36
Output overcurrent
detection signal
Time
ON
Output overcurrent
detection delay time 09-37
Figure 5-23 Schematic diagram of output overcurrent detection
09-38
Arbitrary arrival current 1
Factory setting
100.0%
Setting range 0.0%
~
300.0%(motor rated current)
09-39
Arbitrary arrival current 1 width
Factory setting
0.0%
Setting range 0.0%
~
300.0%(motor rated current)
09-40
Arbitrary arrival current 2
Factory setting
100.0%
Setting range 0.0%
~
300.0%(motor rated current)
Summary of Contents for S3100E Series
Page 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Page 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...