The droop control means that as the load increases, the output frequency of the inverter decreases, so that when
multiple motors drag the same load, the output frequency of the motor in the load decreases more, which can
reduce the load of the motor and realize the The load is even.
09-16
Set cumulative power-on arrival time
Factory setting
0h
Setting range 0h
~
65000h
When the cumulative power-on time (08-13) reaches the power-on time set in 09-16, the inverter's multi-function
output terminal Terminal (function 24) turns on.
09-17
Set cumulative running arrival time
Factory setting
0h
Setting range 0h
~
65000h
Used to set the running time of the inverter.
When the accumulated running time (08-11) reaches this set running time, the inverter's multi-function output
terminal Terminal (function 12) turns on.
09-18
Power-on operation protection options
Factory setting
1
Setting range
0
Run command is valid when power on
1
Run command is invalid when power on
The parameter is 1, if the running command is valid when the inverter is powered on (such as the terminal running
command is closed before powering on), the inverter does not respond to the running command, and the running
command must be canceled once before the inverter is valid again response.
In addition, if this parameter is set to 1, if the running command is valid at the time of inverter fault reset, the
inverter will not respond to the running command, and the running command must be removed before the running
protection state can be eliminated.
Setting this parameter to 1 can prevent the danger caused by the motor responding to the running command
when the power is turned on or the fault is reset without knowing it.
09-19
Frequency detection value(FDT1)
Factory setting
50.00Hz
Setting range 0.00Hz
~
Max frequency
09-20
Frequency detection hysteresis(FDT1)
Factory setting
5.0%
Setting range 0.0%
~
100.0%(FDT1 Level)
When the running frequency is greater than or equal to the frequency detection value, the inverter's multi-function
output terminal (function 3) outputs an ON signal. When the frequency is lower than the detection value by a
certain frequency value, the output ON signal is canceled.
The above parameters are used to set the detection value of the output frequency and the hysteresis value of the
output operation release.Where 09-20 is the percentage of the hysteresis frequency relative to the frequency
detection value 09-19. Figure 5-17 is a schematic diagram of the FDT function.
Summary of Contents for S3100E Series
Page 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Page 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...