129
In application, the corresponding multi-function input terminal function needs to be set to "length count input"
(function 27). When the pulse frequency is high, the MI5 port must be used.
13-08
Set count value
Factory setting
1000
Setting range 1
~
65535
13-09
Designated count value
Factory setting
1000
Setting range 1
~
65535
The count value needs to be collected through the multi-function digital input terminal. The application needs to
set the corresponding multi-function input terminal function to "counter input" (function 25). When the pulse
frequency is high, the MI5 port must be used.
When the count value reaches the set count value 13-08, the multi-function output terminal (function 8) outputs an
ON signal, and then the counter stops counting.
When the count value reaches the designated count value 13-09, the multi-function output terminal (Function 9)
outputs an ON signal. At this time, the counter continues to count until the "set count value" stops the counter.
The designated count value 13-09 should not be greater than the set count value 13-08.
Figure 5-30 is a schematic diagram of the set count value arrival and designated count value arrival functions.
Designated count value
relay
Set count value
MO1
Count pulses
MI5
1
9
8
7
6
2
5
4
3
Figure 5-30 Schematic diagram of set count value and designated count value
17 Torque Control Parameters
17-00
Speed/torque control method selection
Factory setting
0
Setting range
0
Speed control
1
Torque control
Select the control method of the inverter.
The S3100E's multi-function input M I terminal has two functions related to torque control: torque control
prohibition (function 29) and speed control/torque control switching (function 46). These two terminals should be
used in conjunction with 17-00 to achieve the switching between speed and torque control.
When the speed control/torque control switching terminal is invalid, the control mode is determined by 17-00. If
the speed control/torque control switching is effective, the control mode is equivalent to the reverse of the value of
17-00.
When the torque control inhibit terminal is valid, the inverter is fixed to speed control mode.
Summary of Contents for S3100E Series
Page 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Page 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...