Rotation speed tracking mode
Factory setting
0
Setting range
0
Start from stop frequency
1
Start from zero speed
2
Start from maximum frequency
In order to complete the speed tracking process in the shortest time, choose the method of inverter tracking:
0: Track down from the frequency of power failure, this method is usually selected.
1: Start tracking from 0 frequency and use when the power is off for a long time before restarting.
2: Track down from the maximum frequency, generally used for generating loads.
07-15
Rotation speed tracking speed
Factory setting
20
Setting range 1
~
100
When the speed tracking is restarted, select the speed of the speed tracking.
The larger the parameter, the faster the tracking speed.However, if the setting is too large, the tracking effect may
be unreliable.
08 Man-machine Interface Parameters
08-00
User password
Factory setting
0
Setting range 0
~
65535
08-00 sets any non-zero number, the password protection function takes effect. The next time you enter the menu,
you must enter the password correctly, otherwise you cannot view and modify the function parameters, please
remember the set user password.
Set 08-00 to 00000, then clear the set user password and invalidate the password protection function.
08-01
QUICK/JOG key function selection
Factory setting
3
Setting range
0
QUICK/JOG invalid
1
Keyboard command channel and remote command channel (terminal
Terminal command channel or communication command channel) switch
2
Forward and reverse switching
3
Forward jog
4
Reverse jog
QUICK/JOG is a multi-function key, and the function of QUICK/JOG key can be set through this parameter. You
can use this key to switch between stop and running.
0: This button has no function.
1: Switch between keyboard command and remote operation. Refers to the switching of the command source,
that is, the switching between the current command source and the keyboard control (local operation).If the
current command source is keyboard control, the function of this key is invalid.
2: Forward and reverse switching Use this key to switch the direction of the frequency command. This function is
only valid when the command source is the command channel of the operation panel.
3: Forward jog (FJOG) can be achieved through this key.
4: Reverse jog (RJOG) can be realized through this key.
Summary of Contents for S3100E Series
Page 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Page 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...