113
10-20
PID parameter switching deviation 2
Factory setting
80.0%
Setting range 10-19
~
100.0%
In some applications, a group of PID parameters cannot meet the requirements of the entire operation process,
and different PID parameters need to be used in different situations.
This group of parameters is used to switch between two groups of PID parameters. The setting method of the
parameters 10-15~10-17 of the regulator is similar to the parameters 10-05~10-07.
The two sets of PID parameters can be switched through the multi-function input MI terminal l, and can also be
automatically switched according to the deviation of PID.
When switching through the multi-function MI terminal l, the function selection l of the multi-function terminal l
should be set to function 43 (PID parameter switching terminal l), when the terminal l is invalid, select the
parameter group 1 (10-05~10-07), When terminal l is valid, select parameter group 2 (10-15~10-17).
When the automatic switching is selected, the absolute value of the deviation between the given and feedback is
less than the PID parameter switching deviation 1 10-19, PID parameter selection parameter group 1. When the
absolute value of the deviation between the reference and feedback is greater than the PID switching deviation 2
(10-20), PID parameter selection selects parameter group 2.When the deviation between reference and feedback
is between switching deviation 1 and switching deviation 2, the PID parameters are the linear interpolation values
of the two groups of PID parameters, as shown in Figure 5-26.
PI parameter
PI parameter 1
10-05
、
10-06
、
10-07
PID deviation
PI parameter 2
10-15
、
10-16
、
10-17
10-19
10-20
Figure 5-26 PID parameter switching
10-21
PID Initial value
Factory setting
0.0%
Setting range 0.0%
~
100.0%
10-22
PID initial value hold time
Factory setting
0.00s
Setting range 0.00s
~
650.00s
When the inverter starts, the PID output is fixed at the initial PID value of 10-21, and the PID will start the
closed-loop adjustment operation only after the initial PID holding time of 10-22.
Output frequency
PID initial value
10-21
Time
PID initial value hold time
10-22
Figure 5-27 Schematic diagram of PID initial value function
Summary of Contents for S3100E Series
Page 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Page 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...