![Savch S3100E Series User Manual Download Page 69](http://html.mh-extra.com/html/savch/s3100e-series/s3100e-series_user-manual_1203759069.webp)
65
When the auxiliary frequency source is given as a superposition (that is, the frequency source is selected as X+Y,
X to X+Y switching or Y to X+Y switching), please note:
(1) When the auxiliary frequency source selects the digital setting, the given frequency (00-06) of the keyboard
does not work, and the frequency can
be adjusted by the ▲ and ▼ keys of the keyboard (or UP and DOWN of the
multi-function input terminal). The frequency is adjusted on the basis of the main frequency.
(2) When the auxiliary frequency source selects analog (AVI1, AVI2/ACI) or pulse input as the timing, the input
setting 100% corresponds to the frequency range, which can be set by 00-15 and 00-16.
Note: The setting values of 00-02 and 00-14 cannot be the same, that is, the auxiliary frequency source Y and the
main frequency source X cannot select the same channel, otherwise the operation may be messy.
00-15
Selection of auxiliary frequency source Y range during stacking
Factory setting
0
Setting range
0
Relative to the maximum frequency
1
Relative to the main frequency source X
00-16
Auxiliary frequency source Y range when superimposed
Factory setting
100%
Setting range 0%
~
150%
When the frequency source is selected as "frequency superposition" (that is, 00-17 is set to 1, 3 or 4), these two
parameters are used to determine the adjustment range of the auxiliary frequency source.
00-15 if you select 1 relative to the main frequency source X, the range of the auxiliary frequency source will
change with the change of the main frequency X.
00-17
Frequency source overlay selection
Factory setting
0
Setting range
Single digit
Frequency source selection
0
Main frequnecy source X
1
Main and auxiliary calculation results (the operation relationship is
determined by ten digits)
2
Switch between main frequency source X and auxiliary frequency
source Y
3
Switch between main frequency source X and main and auxiliary
calculation results
4
Switch between auxiliary frequency source Y and main and auxiliary
calculation results
Tens digit
Frequency source main and auxiliary operation relationship
0
Main+auxiliary
1
Main-auxiliary
2
Maximum of both
3
Minimum of both
Use this parameter to select the frequency reference channel. The frequency setting is realized by the
combination of the main frequency source X and the auxiliary frequency source Y.
Single digit: frequency source selection:
0: Main frequency source X
The main frequency X is taken as the target frequency.
1: Main and auxiliary calculation results The main and auxiliary calculation results are used as the target
frequency. For the relationship between the main and auxiliary calculations, please refer to the description of
"Ten" of this parameter.
2: Switch between main frequency source X and auxiliary frequency source Y When multi-function input terminal
function 18 (frequency switching) is invalid, main frequency X is used as the target frequency.
Summary of Contents for S3100E Series
Page 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Page 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...