118
11-49
Fault protection action selection 3
Factory setting
0
Setting
range
Single digit
Reserved
Tens digital
Reserved
hundreds digital Power-on time arrival (EIND) (same as 11-47 digits)
thousands
digital
Lost load(oLL)
0
Coast to stop
1
Stop according to the stop mode
2
Decelerate to 7% of the rated frequency of the motor and continue
to run. If the load is not lost, it will automatically return to the set
frequency.
ten thousands
digital
PID feedback lost during operation (PIDE) (same as 11-47 bits)
11-50
Fault protection action selection 4
Factory setting
Setting
range
Reserved
When "free stop" is selected, the inverter displays the fault code and directly stops.
When "Stop by Stop Mode" is selected: The inverter displays a fault and stops according to the stop mode.
When "Continue running" is selected: The inverter displays a fault and the running frequency continues to run at
the selected frequency of 11-54.
11-54
Continue running frequency selection in case of failure
Factory setting
0
Setting range
0
Run at current operating frequency
1
Run at set frequency
2
Run at upper limit frequency
3
Run at the lower limit frequency
4
Run at abnormal standby frequency
11-55
Abnormal standby frequency
Factory setting
100.0%
Setting range 60.0%
~
100.0%(100.0% corresponds to the maximum frequency 00-03)
When a fault occurs during the operation of the inverter, and the processing method of the fault is set to continue
running, the inverter displays the fault and continues to run at the selected frequency of 11-54. When the
abnormal standby frequency is selected for operation, the value set in 11-55 is a percentage relative to the
maximum frequency.
11-56
Reserved
Factory setting
11-57
Reserved
Factory setting
11-58
Reserved
Factory setting
11-59
Instantaneous power failure action selection
Factory setting
0
Setting range
0
Invalid
1
Deceleration
2
Decelerate to stop
Summary of Contents for S3100E Series
Page 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Page 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...