67
When the upper limit frequency is set by analog or PULSE, 00-21 is used as the offset value of the set value, and
the offset frequency is superimposed on the set upper limit frequency value of 00-20 as the final set value of the
upper limit frequency.
00-22
Acceleration and deceleration time unit
Factory setting
1
Setting range
0
1s
1
0.1s
2
0.01s
S3100E has 3 kinds of acceleration and deceleration time unit selection. When modified, the decimal points of the
4 groups of acceleration and deceleration time will change, and the corresponding acceleration and deceleration
time will also change. In application, pay attention to the specific value of acceleration and deceleration time.
00-23
Base frequency of acceleration and deceleration time
Factory setting
0
Setting range
0
Maximum frequency (00-03)
1
Set frequency
2
100Hz
The acceleration and deceleration time refers to the acceleration and deceleration time from zero frequency to
the frequency set by 00-23. Figure 5-1 is the schematic diagram of acceleration and deceleration time.
When 00-23 is selected as 1,if the set frequency changes frequently, the acceleration of the motor will also follow
the change, so you need to pay attention to it during application.
00-24
Base frequency for UP/DOWN command during running
Factory setting
1
Setting range
0
Running frequency
1
Set frequency
This parameter is valid only when the frequency source is digitally set.
When the ▲, ▼ keys on the keyboard or the terminal UP/DOWN change the frequency, select whether to
increase or decrease based on the running frequency or increase or decrease based on the set frequency.
Note that when 0 is selected, when the inverter is increasing or decreasing when the inverter is in the process of
acceleration and deceleration, the given frequency may change significantly.
00-25
Frequency command resolution
Factory setting
2
Setting range
1
0.1Hz
2
0.01Hz
This parameter is used to determine the number of decimal points for all frequencies, and the frequency
resolution also changes accordingly.
When the frequency resolution is 0.1Hz, the maximum output frequency of S3100E can reach 3200.0Hz,
Summary of Contents for S3100E Series
Page 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Page 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...