Mini ECO-i System
Remote Control Functions
7
7
- 186
12. Serial-Parallel I/O Unit for Each
Indoor Unit (ACC-SP1AG(B))
ON
ON
OFF
1
4
1 2 3 4
0
1
2
3
4
5
6
7
S1
1
2
3
4
8
9
10
11
12
13
14
15
S1
1
2
3
4
: OFF
: ON
JP6
JP5
JP4
JP3
JP2
JP1
JP6
S1
S2
S
ettings switch
Control type setting switch S1
Control
type
Control
type
Refer to digital input.
Detail setting switch S2
Connection
Cut
Connection
Connection
Cut
Cut
Cut
Connection
Cut
Connection
Cut
N/C
N/C
With Remote controller or centralized control
system
Without Remote controller or centralized control
system
(factory default)
(factory default)
(factory default)
(factory default)
(factory default)
(factory default)
JP1
JP3
JP2
Connection
1:
2:
3:
4:
Voltage present / absent switch S3
Set temperature input switch S4
(factory default)
(factory default)
For digital input, switches between
voltage present and voltage absent.
For analog input, switches between
input voltage and input resistance.
JP4
JP5
Input voltage
Input voltage
Output control temperature as room temperature
Output intake temperature as room temperature
Set temperature push priority
Prohibit Remote controller temperature setting
N/C
N/C
Switches the local remote control temperature setting operation between push priority and
operation prohibited.
Switches the room temperature monitor output between the temperature used by the
controller (when heating, the intake temperature with shift, or the remote control sensor)
and the intake temperature.
Cut (fixed voltage) JP4, although no change the setting temperature with Seri-Para I/O
Unit. Do not input voltage to No.3 and 4 (AI ) of CN1 at the time.
When using the Seri-Para I/O Unit, it is standardized to connect a remote controller or a
centralized control system (i.e. System controller). To use the Seri-Para I/O Unit by itself
(without a remote controller or a centralized control system), cut JP5. In this regard,
however, the operational functions (such as operation mode, fan speed and wind direction)
will be limited with only the Seri-Para I/O Unit.
G
The indoor temperature monitor output is
from 4 to 20 mA DC (5 to 36°C), and the
temperature can be set in steps of 0.5°C.
Take care of the measurement units used by
the central monitor. The wiring specifications
are for analog input.
Keep the load resistance below 240
Ω
.
4
Analog output
36
4
20 mA
5
°C
Relationship between current
value and temperature
(example) 3-1: Operation mode of a typical model [lower limit to upper limit
°
C]
Cool (dry) [18 to 30
°
C]
Heat [16 to 26
°
C]
Auto [17 to 27
°
C]
30
℃
0
10
V
18
26
℃
0
10
V
16
27
℃
0
10
V
17
Input voltage
①
0
140
Ω
0
140
Ω
0
140
Ω
Input resistance
06-408 Mini_ECOi_SM7 11/10/06 7:25 PM Page 186