7
- 177
Mini ECO-i System
Remote Control Functions
7
11. Schedule Timer
(SHA-TM64AG(B))
OFF ON
S42
1
2
3
4
5
6
7
8
* These switches
are all OFF at the
time of delivery.
If remote controller enable/disable is used,
this switch sets the range for remote
controller enable (cancel).
Enable all items* that can be controlled
with the remote controller.
OFF
Enable only the items determined by
setting switches 2, 3, and 4.
ON
This switch should be OFF for normal use,
or when remote controller enable/disable is
not used.
Remote Controller Enable Items (1)
* This refers to the following items: start/stop,
operation mode, temperature setting, flap,
and fan speed.
OFF OFF
OFF OFF
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Spare (6, 7, 8)
Temperature s Operation mode + Start/stop
Remote Controller Disable Item Switches (2, 3, 4)
When timer remote controller disable is used, set the remote controller
disable item switches according to the items for which remote
controller operation will be disabled.
Remote controller disabled items
2
3
4
Remote controller disable not used
Start/stop
Operation mode
Operation mode + Start/stop
Temperature setting
Temperature s Start/stop
Temperature s Operation mode
Central 1 – 4 are the designations for the remote-controller disable
modes for the system controller.
Central 1
Central 4
Central 2
Central 3
When multiple schedule timers are installed, set this switch to ON to
perform time settings for multiple units simultaneously. One minute
after the time is set, the time at the other schedule timers will change
to match the set time. (Ordinarily this switch is OFF.)
Simultaneous time communications (5)
Disabled: OFF Enabled: ON
Be sure that these switches are OFF when the system is used.
Creating Timer Groups
The schedule timer can be set for 6 time status changes. These can be
used to create up to 8 groups (timer groups). For systems in which sched-
ule timers are used, set the timer groups to match the central control
addresses of the indoor units that will be subject to group timer control.
The timer-group settings for the schedule timer involve assignment of
central control addresses. Therefore, use the system controller (or other
central control device) or wired remote controllers to set the central con-
trol addresses of the indoor units, then make the schedule timer settings.
1
2
17
18
33
34
49
50
8
24
40
56
9
25
41
57
10
26
42
58
16
32
48
64
[Setting fixed timer groups]
Schedule timer
1 fixed timer group (64 units together)
4 fixed timer group (16 units together)
8 fixed timer group (8 units together)
Central control address 1 – 64
Central control address 1 – 16
Central control address 1 – 8
Central control address 17 – 24
Central control address 17 – 32
Central control address 33 – 40
Central control address 33 – 48
Central control address 49 – 64
Central control address 49 – 56
Central control address 57 – 64
Central control address 41 – 48
Central control address 25 – 32
Central control address 9 – 16
06-408 Mini_ECOi_SM7 11/10/06 7:25 PM Page 177