Mini ECO-i System
Remote Control Functions
7
7
- 184
12. Serial-Parallel I/O Unit for Each
Indoor Unit (ACC-SP1AG(B))
(open)
(open)
(close)
(close)
(open)
(close)
(open)
(close)
(open)
(close)
(open)
(close)
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1 Digital input
G
Select the control type using control type setting switch S1, according to
the table below.
Control
type
Input1 (DI 1)
Input2 (DI 2)
Input3 (DI 3)
Start
Fan low
Start
Prohibit R/C
Start/Stop
Indoor units stop
when all of Input
1, 2, 3 are open
Stop
Prohibit R/C
Start/Stop
Start
Prohibit R/C Start
Start <-> Stop
Prohibit R/C
Start/Stop
Start
Prohibit R/C
Start/Stop
Start
Prohibit R/C Start
Start
Accept R/C
Start/Stop
Start <-> Stop
Prohibit R/C
Start/Stop
Heat
Heat
Start
-
Stop
Prohibit R/C
Start/Stop
Indoor units stop
when all of Input
1, 2, 3 are open
Start
Fan medium
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Start
Accept R/C
Start/Stop
Accept R/C
Start/Stop
Start <-> Stop
Accept R/C
Start/Stop
Start
Accept R/C
Start/Stop
Accept R/C
Start/Stop
Stop
Accept R/C
Start/Stop
Start <-> Stop
Accept R/C
Start/Stop
Cool
Cool
Start
Indoor units
stop when all of
Input 1, 2, 3 are
open
Stop
Prohibit R/C
Start/Stop
Stop
Prohibit R/C
Start/Stop
Indoor units stop
when all of Input
1, 2, 3 are open
-
-
-
-
-
-
-
Start
Fan high
Stop
Prohibit R/C
Start/Stop
Stop
Prohibit R/C
Start/Stop
Stop
Prohibit R/C
Start/Stop
Stop
Prohibit R/C
Start/Stop
Stop
Prohibit R/C
Start/Stop
Set thermostat
OFF
-
Fan
Fan
Start
Indoor units
stop when all
of Input 1, 2, 3
are open
Release
thermostat OFF
Set thermostat
OFF
Release
thermostat OFF
-
-
-
-
-
-
Indoor units
stop when all
of Input 1, 2, 3
are open
R/C: Remote Controller
Start
Stop
Type:
vinyl insulated cord with sheath
Thickness: 0.5 to 2.0 mm
2
Length:
100 m maximum
2
Digital output
G
Wiring specifications
G
D01 for start output signal.
D02 for alarm output signal.
G
Maximum allowable contact voltage and current are AC 240 V and 3 A
maximum or DC24 V and 3 A maximum.
G
Wiring specifications are for digital input.
1:
When inputting pulses, set the pulse width to 200 ms.
Voltage a-
contact
static/pulses
1
All input: static
Input 1, 2: static
Input 3: pulse
Input 1, 2: static
Input 3: pulse
All input: pulse
Input 1, 2: pulse
Input 3: static
All input: pulse
All input: static
All input: static
-