Mini ECO-i System
Remote Control Functions
9. LonWorks Interface Product Manual
(SHA-LN16UG(B))
㧖
The following is intended for the installer responsible for
installation and test operations of the LonWorks Interface, and
should be carefully read before beginning.
㧖
The precautions given in this manual consist of specific
“Warnings” and “Cautions.” They provide important
safety-related information and are important for your safety, the
safety of others, and trouble-free operation of the system. Be sure
to strictly observe all safety procedures. The labels and their
meanings are as described below.
This symbol refers to a hazard or unsafe
procedure or practice which can result in
severe personal injury or death.
This symbol refers to a hazard or unsafe
procedure or practice which can result in
personal injury or product or property
damage.
̪
After installation is completed, perform a test run to check for
operating trouble. As you do, use the central control device
Operation Manual
and explain operating procedures to the
customer. Then request that the customer store this manual
together with the central control device
Operation Manual.
Warning
N
Be sure to arrange installation from the dealer where the system
was purchased or using a professional installer.
Electric shock or fire may result if an inexperienced person
performs any installation or wiring procedures incorrectly.
N
Please install and ensure construction according to
Procedures
for Installation (Electrical Work) of LonWorks Interface.
N
Only a qualified electrician should attempt to connect this
system, in accordance with the instructions in this manual. And
be sure to use a dedicated electrical circuit.
If the electrical circuit capacity is insufficient a danger of
electric shock and fire may be present.
N
Use the specified cables (type and wiring diameter) for the
electrical connections, and connect the cables securely. Run and
fasten the cables securely so that external forces or pressure
placed on the cables will not be transmitted to the connection
terminals. Overheating or fire may result if connections or
attachments are not secure.
Caution
Depending on the installation conditions and location, an earth
leakage breaker may be required. If an earth-leakage breaker is
not installed, there is a danger of electric shock or fire.
Safety Precautions
N
Install using either of the 2 methods given below.
The screws used to install the main unit must be provided by the
installer.
N
Install the LonWorks Interface away from any sources of
electrical noise.
Installation Method
2. Procedures for Installation (Electrical Work) of LonWorks Interface
Warning
Caution
Included parts
No. Part Qty
(1) 1
Included Parts
Horizontal installation
Vertical installation
N
For the indoor/outdoor control lines use twin-core 0.5 – 2 mm
2
shielded cables and ground the shield on both side.
N
For the LonWorks communication line cables, use twisted-pair
cables with a wire diameter of 0.51 mm or larger as
recommended by Echelon Corp.
Examples of cables recommended by Echelon Corp
Total cable length
Cable type
Wire diameter
/AWG
Bus type
Free
24 AMG twisted-pair
(TIA568A category 5)
0.51mm
/24
900m 450m
N
Do not use the same cable for the indoor/outdoor control lines,
the LonWorks communication lines, and the power cable. Do not
run them through the same conduit or place the cables near one
another.
N
Connect the cables so that there is no miswiring.
(Miswiring can cause malfunction.)
Wiring Specifications
Product manual
06-408 Mini_ECOi_SM7 11/10/06 7:24 PM Page 137