Mini ECO-i System
Monitor Functions
1. Calling the Sensor
Temperature Display
<Description>
From the remote controller it is possible to engage
service monitor mode to determine the temperature
at the remote controller, indoor unit, and outdoor unit
sensors.
<Procedure>
Refer to the remote controller display shown in Fig. 1
Press and hold the
(CANCEL) and
(TEST/CHK) buttons simultaneously for 4 sec-
onds or longer to engage service monitor mode.
The service monitor illuminates. Initially, the main
indoor unit No., and the temperature for item
code
, are displayed.
Press the temperature setting
/
buttons to change the sensor number (item code)
to the sensor you wish to monitor. The sensor
numbers are listed on table 1 (below).
Press the
(UNIT SELECT) button and
change to the indoor unit that you wish to monitor.
The sensor temperatures of the indoor units
under group control and the corresponding out-
door unit are monitored.
Press the
(TEST/CHK) button to return to
normal display.
4
3
2
1
2
3
1
4
Fig. 1
Procedure:
Returns to normal display.
1
2
3
4
Indoor
Unit
Data
Outdoor
Unit
Data
Item code
Data name
00
01
02
0
3
04
05
06
08
0A
0b
0C
0d
0E
11
Room temperat
u
re (co
n
trol i
n
effect) *
Room temperat
u
re (remote co
n
troller)
I
n
door
su
ctio
n
temperat
u
re
I
n
door heat excha
ng
er temperat
u
re (E1)
–
I
n
door heat excha
ng
er temperat
u
re (E
3
)
Di
s
char
g
e air temperat
u
re (BL)
Po
s
itio
n
of i
n
door
un
it motor operated valve (MOV)
Di
s
char
g
e temperat
u
re (TD)
–
–
Su
ctio
n
temperat
u
re (T
S
)
O
u
tdoor heat excha
ng
er temperat
u
re (C1)
O
u
tdoor air temperat
u
re (TO)
* Mai
n
un
it o
n
ly i
n
the ca
s
e of
g
ro
u
p co
n
trol
Table 1