7
- 103
Mini ECO-i System
Remote Control Functions
7
6. Intelligent Controller
(SHA-KT256BG)
12 Supplementary Information
IMPOR
TANT
•
Microsoft and
Windo
ws CE are trademar
ks of Microsoft Cor
poration in the United States and other
countries.
Other products names are trademarks or registered trademarks of their respective holders, or
cop
yr
ights of their respectiv
e holders
.
•
Duplication of all or par
t of the softw
are and documentation of this product without the e
xpress
consent of the holder of the r
ights to the abo
v
e
, and transf
er of the softw
are to another par
ty
, are
prohibited b
y
la
w
.
•
San
y
o will not be liab
le f
or an
y loss
, lost profits
, or an
y incidental damages due to use of this product
or the supplied softw
are
. San
y
o will not be liab
le to an
y claim based on a third-par
ty claim.
Ev
en in the case of errors in calculations of distr
ib
ution r
atios
, and so on, San
y
o will not be
responsib
le f
or an
y remedies
.
•
The softw
are supplied with this product ma
y not be used on an
y other equipment.
•
This product and the supplied softw
are are subject to change without notice
.
The contents of this manual are subject to change without notice
.
•
San
y
o will not be liab
le f
or an
y violation of the r
ights of an
y third par
ty stemming from use of
inf
or
mation in this man
ual, or f
or violation of other r
ights
.
Before requesting service, check the following items.
Do not attempt to service the Intelligent Controller yourself. Doing so can be dangerous.
Symptom
Nothing appears on the screen when the
computer is tur
ned on.
Timer oper
ation does not w
o
rk
.
The distr
ib
ution r
atio is alw
a
ys 100%.
The po
w
er goes off at odd times
.
There is an alar
m message in the
notification bar at the bottom of the screen
that will not go a
w
a
y.
Bac
king up to a PC Card does not w
o
rk
.
It tak
es a long time after an oper
ation f
o
r
the screen to be updated.
LCD displa
y
Nothing happens when an oper
ation
button is pressed.
When local remote control operation is
prohibited on the Intelligent Controller
, the
Intelligent Controller is not ab
le to star
t/
stop operation of a malfunctioning air
conditioner
.
A po
w
er outage occurred.
When it ended,
the equipment did not come on
automatically according to prog
ram timer
settings
.
The Intelligent Controller cannot find a
single indoor unit. Or it cannot find all of
them.
A message of “Application error!!” is
displa
y
ed and the unit does not star
t.
Cause
•
Is the power cord connected?
•
Is the po
w
er s
witch set to on?
•
Is timer operation set to the target unit? Operation of a selected
timer does not star
t if the setting is not set the target unit.
•
Does the setting match the current date and time?If the
date and time do not match, oper
ation can star
t at an
unexpected time. (See “6.3.2 Setting the date, cut-off date,
and distribution ratio calculation method”)
•
Check the group settings and tenant settings.
Distr
ib
ution r
ate calculations alw
a
ys result in 100% if there
is only one tenant registered in a distribution group, or if
there is only one indoor unit in a tenant.
•
The screen ma
y be b
lank because of the po
w
er-sa
ving auto
off function.
The Intelligent Controller is still po
w
ered on.
T
ouch the screen to restore the displa
y.
•
Regardless of the selected auto off time
, the screen ma
y be
turned off when the Intelligent Controller boots.
•
The message displays the unit where the alarm occurred,
and the alar
m n
umber
. Inf
or
m y
our dealer or ser
vice
pro
vider about the content of the message
.
•
Data can be bac
k
ed up only to the special PC Cards
(option) f
or the Intelligent Controller
. Bac
kup to other PC
Card types is not possib
le
.
•
A cer
tain amount of time ma
y be required depending on the
state of comm
unications with the connected air conditioners
.
Please w
ait until all of the inf
or
mation is receiv
ed.
•
In rare cases there may be a dot on the screen which is
alw
a
ys on or alw
a
ys off
.
This is not a malfunction.
Due to
the nature of LCD displays, there may be some color
b
leeding in cer
tain areas because of v
a
riations in
temperature and so on.
This is nor
mal and not a malfunction.
•
Ov
er e
xtended use
, the touch positions and displa
y
positions on the touch panel may get out of alignment.
(
¡
“6.8.9.7. Calibrating touch panels”)
•
Emergency operations until our service person arrives:
P
o
w
er off the Intelligent Controller and e
xter
nally installed
communication adapter; re-power on the indoor unit. Operation
with the local remote control will be possib
le
. Ho
w
e
ve
r,
this
cannot be done in a remote control free system.
•
The Intelligent Controller does not power on equipment
automatically b
y prog
ram timer after a po
w
er outage
.
The
setting for the next programmed time will be executed
when the time arrives.
•
T
ry using the
“Chec
k configur
ation”
b
utton in the
“Other
settings” screen (
Main
Sub
6
6
9
9
).
•
Contact the store where you purchased the system or our
ser
vice agency
.
13 T
roub
leshooting
06-408 Mini_ECOi_SM7 11/10/06 7:24 PM Page 103