6
- 12
Mini ECO-i System
Service Checker
6. Setting Mode
6
This function is used to make the outdoor unit EEP-
ROM settings.
Setting mode 1
Press the
(CHECK) button and the
(VENTILATION) button simultaneously for 4 sec-
onds or longer.
Press the temperature setting
/
buttons to change the item code. The item codes
and setting data are shown in the table below.
Press the timer time
/
buttons to change
the setting data.
To confirm the changed setting data, press the
(
S
ET) button.
(At this time, the
(
S
ETTING) display
stops blinking and remains lit.)
(
S
ETTING) blinks when this mode is
engaged, and “
” appears in the outdoor unit
address section. The item code number (values
shown in the table below) and the corresponding
setting data (6 digits) are also displayed. (The 6
digits of the setting data are displayed by changing
between the first 3 digits (Fig. A) and the last 3
digits (Fig. B). When the first 3 digits are displayed,
the bottom dot of the colon is illuminated.)
To exit setting mode, press the
(CHECK)
button. Return to normal display mode.
S
nowfall sensor usage
Outdoor unit fan Quiet mode
Energy
S
aving mode
Energy saving operation plug
Demand 1 current
Demand 2 current
0 =
S
ensor input not present. Control is performed.
1 =
S
ensor input present. Control is performed.
2 =
S
ensor input not present. Control is not performed.
3 =
S
ensor input present. Control is not performed.
0 = Disabled
1 = Quiet mode 1
3 = Quiet mode 3
2 = Quiet mode 2
4 = Quiet mode 4
0 = None
1 = Discharge temp. control only (Mode 3)
2 = Demand only (Mode 2)
3 = Discharge temp. c Demand (Mode 1)
0 = Independent
1 = All indoor units linked
0 = 0% 1 = 40 … 4 = 70 7 = 100
8
= 120
9 = 140 10 = 160 11 = 200 12 = –1 (no limit)
0 = 0% 1 = 40 … 4 = 70 7 = 100
8
= 120
9 = 140 10 = 160 11 = 200 12 = –1 (no limit)
DN
Parameter
Description
(A) and (B) are displayed alternately.
(A)
(B)
06-408 Mini_ECOi_SM6 11/10/06 5:22 PM Page 12