Mini ECO-i System
Remote Control Functions
12. Serial-Parallel I/O Unit for Each
Indoor Unit (ACC-SP1AG(B))
3
Analog input
Note:
Input voltage after an indoor unit has been connected.
The maximum input voltage is 10 V. Over 10 V input voltage may cause malfunction.
0-10V
4
3
2
1
AI+
AI-
AO+
AO-
S4
Relationship between connection
resistance and temperature
Line connection
0
140
Upper
temperature
limit setting
Lower
temperature
limit setting
°C
0-140
Ω
0-10V
0-10V
4
3
2
1
AI+
AI-
AO+
AO-
G
S4
Relationship between input
voltage and temperature
Line connection
0
10 V
Upper
temperature
limit setting
Lower
temperature
limit setting
°C
●
In case of Input voltage
,
●
Input voltage
(equally divided upper and lower setting temperature limits)
(factory default)
・
Performed in the input range of 0 to 10 V DC (lower setting
temperature limit to upper setting temperature limit).
・
Relationship between setting temperature and voltage is as the diagram below.
・
Upper and lower temperature setting limits may vary according to the indoor units and
operation mode.
Refer to the relationship between setting temperature and voltage, described in (example)
3-1 "Operation mode of a typical model [lower limit to upper limit]".
・
Set the Set temperature input switch S4 to "0 to 10 V" (factory default)
・
Wiring specifications
Type:
vinyl insulated cord with sheath (shield line recommended)
Thickness: 1.25 to 2.00 mm
2
Length:
70 m maximum
●
Select the temperature setting control method from the following 3 types.
・
Input voltage
(equally divided upper and lower setting temperature limits)
・
Input voltage
(fixed voltage)
・
Input resistance
・
Performed in the input range of 0 to 10 V DC.
・
The effective range of the setting temperature is 2.2 V to 10 V (11 °C to 50 °C).
Remote controller cannot be used for temperature in this range.
・
When the input exceeds the upper or lower setting temperature limits, it is set to the upper or
lower limits.
For example, in case of air-conditioning (cool) [18 °C to 30 °C], if the voltage is below 3.5 V,
the temperature is set to 18 °C, and if over 6.2 V, to 30 °C.
・
To set the temperature using remote controller, set the input voltage below 1.9 V.
50
℃
11
0
1.9 2.2
10.0
V
Remote controller
cannot be used for
temperature setting.
Remote controller
can be used for
temperature setting.
0-140
Ω
0-10V
0-10V
4
3
2
1
AI+
AI-
AO+
AO-
G
JP6
JP5
JP4
JP3
JP2
JP1
JP4 cut
●
Input voltage
(fixed voltage)
Mapping table of setting temperature and input voltage (input voltage
)
Temperature
setting
[ °C]
Input voltage
[V]
1 6
1 7
1 8
1 9
2 0
2 1
2 2
2 3 2 4
2 5
2 6
2 7
2 8
2 9
3 0
3.2 3.4 3.6 3.8 4.0 4.2 4.4 4.6 4.8 5.0 5.2 5.4 5.6 5.8 6.0
・
Temperature setting (1 °C step) is performed in the range of 0 to 140
Ω
.
・
Relationship between setting temperature and resistance is as the diagram below.
・
Upper and lower temperature setting may vary according to the indoor units and operation mode.
Refer to the relationship between setting temperature and resistance, described in (example) 3-1
"Operation mode of a typical model [lower limit to upper limit]".
・
Set the Set temperature input switch S4 to "0 to 140
Ω
".
・
Wiring specifications
Type:
vinyl insulated cord with sheath (shield line recommended)
Thickness: 1.25 to 2.00 mm
2
Length:
70 m maximum
●
Input resistance
06-408 Mini_ECOi_SM7 11/10/06 7:25 PM Page 185