Mini ECO-i System
Service Checker
5. Outdoor Unit Alarm History Monitor
6
Recalls and displays the outdoor unit alarm history.
•
This is for the outdoor unit only. Indoor unit alarms
cannot be recalled.
•
The indoor unit alarm history can be viewed on the
indoor unit remote controller or other controller.
<Operation procedure>
Press and hold the
(CHECK) button and
(
S
ET) button simultaneously for 4 seconds or
longer to engage outdoor unit alarm history mode.
During temperature monitoring,
(CHECK)
illuminates.
Press the temperature setting
/
but-
tons and select the item code for the alarm history.
The selected outdoor unit address, the item code,
and the alarm history (alarm data) are displayed.
The outdoor unit address is displayed as R.C.
XX – YY.
(R.C. XX = Outdoor unit system address)
YY = Outdoor unit sub-bus address (always “1” for
Mini ECO-i units)
Unit codes 01 – 0
8
are displayed. 01 indicates the
most recent alarm.
The alarm history displays the alarm code. (If no
alarms are present, then
is displayed.)
To clear the alarm history, press the
(CANCEL) button. (The outdoor unit alarm history
will be cleared.)
To exit, press the
(CHECK) button.
Return to normal display mode.
NOTE