Mini ECO-i System
Remote Controller Functions
1. Remote Controller Test Run Settings
2
Wired Remote Controller Test Run Settings
1. Press the remote controller
button for 4 seconds or longer.
2. “TEST” appears on the LCD display while the test run is in progress.
3. Then press the
button.
G
The temperature cannot be adjusted when in Test Run mode.
(This mode places a heavy load on the machines. Therefore use it only when performing the test run.)
G
The test run can be performed using the HEAT, COOL, or FAN operation modes.
Note:
The outdoor units will not operate for approximately 3 minutes after the power is turned ON and after operation is
stopped.
G
If correct operation is not possible, a error code is displayed on the remote controller LCD display.
(Refer to “Table of Self-Diagnostic Functions” and correct the problem.)
4. After the test run is completed, press the
button again. Check that “TEST” disappears from the LCD display.
G
To prevent continuous test runs, this remote controller includes a timer function that cancels the test run after 60 minutes.
G
The operation is possible even if the cassette-type ceiling panel has not been installed. (“P09” display does not occur.)