Mini ECO-i System
Remote Control Functions
7
8. Local Adaptor for ON/OFF
Controller (SHA-KL4UG(B))
Connection as a Relay Control Unit
The local adapter output terminal and input terminal specifications are given
below.
Use the signals most appropriate for the type of equipment being controlled.
(1) Output terminals
The local adapter provides four styles of ON (set relay) and OFF (reset relay)
output signals for use by the equipment being controlled. Select the style
appropriate for your application. For more information, see the "Relay Circuit
Examples" section.
Setting method
Contact capacity (resistive load)
Pulse contact output
ON (set) output:
a contact
OFF (reset) output:
a contact
Pulse contact output
ON (set) output:
a contact
OFF (reset) output:
b contact
Pulse contact output
ON (set) output:
a contact
Both start and stop
signals are sourced in
turn from the ON (set)
relay
Static contact output
(continuous contact)
S2-1: OFF
S2-4: OFF
S003: NO
S2-1: OFF
S2-4: OFF
S003: NC
S2-1: OFF
S2-2: OFF
S2-4: ON
Only the ON contact
output is used.
The OFF contact
output becomes a
local prohibit signal
(see
2)
S2-1: ON
Only the ON contact
output is used.
The OFF contact
output becomes a
local prohibit signal
(see
2)
ON (set) relay output
(CN1, terminals 6 and 7)
OFF (reset) relay output
(CN1, terminals 8 and 9)
250 V AC, 10 A (inductive load: 5 A)
Minimum usable load: 5 V, 100 mA
250 V AC, 3 A
Minimum usable load: 5 V, 100 mA
Operation answer-
back input
Alarm signal input
Thermo ON signal
input
Local start/stop
input
No-voltage a contact
(static)
No-voltage a contact
(static)
No-voltage a contact
(static)
No-voltage a contact
(pulse)
Monitor the operation
(start/stop condition)
Monitor general
alarms
Monitor the load when
the thermo is ON, and
report to the central
control unit
Equipment ON/OFF
from local adapter
Circuit contact voltage and current: 12 V DC, 10 mA
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
1
1
1
Output style
Contact outputs (relay contact)
Output
1 The pulse width is approximately 0.5 seconds.
2 The output changes according to a signal from the Central control unit.
Use this signal as needed.
< Contact capacity >
Input
Terminal
numbers
1, 2
1, 3
1, 4
1, 5
Input style
Usage
Caution:
Note that the ON (set) relay output and OFF (reset) relay output have different
contact capacities.
(2) Input terminals
Status monitor signals from the equipment being controlled are received
by the relay contacts.
The local start/stop input uses a pulse style, so connect it to a
momentary input device, such as a push switch.
Individual permission:
Local prohibit:
OFF (continuous contact)
ON (continuous contact)
Caution:
When local prohibit (central) is set by the central control unit, the local
start/stop input will be ignored.
When stopped, the alarm input will be ignored.