2nd Edition of TEMP2000M_Series IM : April. 8. 2014 Page 67 / 176
5.5 Standby operation
▶
It is a screen to set the standby range and time to standby during program operation
▶
The set standby operation here is applied to [5.1 Program pattern setting].
※
Definition on standby operation
Condition for entering the standby operation
☞
When the measured data do not enter to the standby operation setting range within segment time.
Condition for releasing the standby operation
☞
When the measured data enters to the standby operation within segment time.
When the standby time is not set (initial value), the standby time shall have the infinite value.
①
It sets Y/N of using the standby operation.
②
It sets the operation range to adapt the standby operation.
③
When the measured data do not enter the standby operation range, the standby time to be applied is
set.
☞
When the standby operation time is set as 00.00, it standby infinitely until entering to the standby
operation range.
④
It sets the standby operation method in “Total” or “SEG Maintain.”
☞
When the entire is set, the standby operation is applied to the entire segment set in [5.1 Program
pattern setting].
☞
When the SEG Maintain is set, the standby operation is applied only to the segment for maintain range
which is set in [5.1 Program pattern setting].
Table 5-5. Standby operation setting parameter
Parameter
Setting range
Unit
Initial data
Standby operation setting
Non-use, Use
ABS
Non-use
Standby operation range
EUS(0.00~100.00%)
EUS
EUS(0.00%)
Standby operation time
0.00~99.59 (Hr.Min)
ABS
00.00
Standby operation type
Entire, SEG Maintain
ABS
Entire
[Fig. 5-10] Screen for setting the standby operation
①
②
④
③