SAMWONTECH
2nd Edition of TEMP2000M_Series IM : April. 8. 2014 Page 121 / 176
15.2 Inner signal operation
▶
While “target value” carries out the same operation with “target value” of programmed control when
change ratio (SLOPE) is set in stationary operation, “target value” carry out the operation with “set value
(SP) when change ratio (SLOPE) is not set in stationary operation.
Setting
Inner signal operation
▶ Input = 0.0 ~ 100.0
→ EUS 0.5% = 0.5
▶ Operation Type =
Pattern
▶ TYPE =
Target Value(PV)
▶ Range Low = 30.0%
▶ Range High = 50.0%
▶ Oper. Band =In Band
(INB)
▶ Delay Time = 00.00
▶ Input = 0.0 ~ 100.0
→ EUS 0.5% = 0.5
▶ Operation Type =
Pattern
▶ TYPE =
Target Value (PV)
▶ Range Low = 30.0%
▶ Range High = 50.0%
▶ Oper. Band = Outside
Band (OUTB)
▶ Delay Time = 00.00
▶ Input = 0.0 ~ 100.0
▶ Operation Type =
Pattern
▶ TYPE = Set Point(SP)
▶ Range Low = 30.0%
▶ Range High = 50.0%
▶ Oper. Band =In Band
(INB)
▶ Delay Time = 00.10
▶ Input = 0.0 ~ 100.0
▶ Operation Type =
Pattern
▶ TYPE=Target Set
Point (TSP)
▶ Range Low = 30.0%
▶ Range High = 50.0%
▶ Oper. Band = Outside
Band (OUTB)
▶ Delay Time = 00.00
50.0
SEG1 SEG2 SEG3 SEG4 SEG5
30.0
ON
OFF
IS
HYS
50.5
HYS
29.5
PV
INB
HYS
49.5
HYS
30.5
50.0
SEG1 SEG2 SEG3 SEG4 SEG5
30.0
ON
OFF
IS
PV
OUTB
OUTB
50.0
SEG1 SEG2 SEG3 SEG4 SEG5
30.0
ON
OFF
IS
SP
INB
DELAY TIME
50.0
SEG1 SEG2 SEG3 SEG4 SEG5
30.0
ON
OFF
IS
SP
OUTB
OUTB