2nd Edition of TEMP2000M_Series IM : April. 8. 2014 Page 127 / 176
▶
If type of alarming is set to AH.F and DO.FS in the [Fig. 17-3 Alarming signal setting the 2
nd
screen],
the following screen is displayed.
①
Alarming set value is set.
②
Hysteresis which applies during alarming operation is set.
③
If the condition of alarming signal is met, actual alarm is generated after the time set for delay time is
passed.
④
Upper limit deviation value is set in case of deviation alarming.
⑤
Lower limit deviation value is set in case of deviation alarming.
Table 17-2. Alarming signal setting the 2
nd
screen
Parameter
Setting range
Unit
Initial data
Alarming#n type
Non-use, AH.F, AL.F, DH.F
DL.F, DH.R, DL.R
DO.F, DI.F, AH.R
AL.R, AH.FS, AL.FS
DH.FS, DL.FS, DH.RS
DL.RS, DO.FS, DI.FS
AH.RS, AL.RS
ABS
Non-use
Alarming#n POINT
EU(-5.0~105.0%)
EU
EU(100.0%)
(Alarming#n type =
not Deviation Alarm)
Alarming#n upper
limit POINT
EUS
Alarming#n lower
limit POINT
EUS(-100.0~100.0%)
EUS
EUS(0.0%)
(Alarming#n type =
Deviation Alarm)
Alarming#n
hysteresis
EUS(0.0~100.0%)
EUS
EUS(0.5%)
Alarming#n delay
time
0.00~99.59 (MIN.SEC)
ABS
00.00
* #n : 1 ~ 4
[Fig. 17-4] Alarming signal setting the2nd screen-3
①
②
③
④
⑤